56
Holding
Register
Type
Value
Comments
40028
Read / Write Reset Fan
Mode
0 = Leave Fan Mode Unchanged
1 = Reset Fan To Auto At Switch Off
40029
Read / Write Belimo Mode
0 = Standard 0 to 10V Valve Logic
1 = Belimo 6V = Off 3 Way Valve Logic
40030
Read / Write Modbus
Address
1 to 255
40031
Read / Write Baud Rate
1 = 4.8Kbs
2 = 9.6kbs
3 = 19.2Kbs
40032
Read Only
Digital Input
Status
0 = Open
1 = Closed
40033
Read Only
Internal
Sensor Value
Value / 10 (e.g. 23.3°C = 233)
40034
Read Only
Remote
Sensor Value
Value / 10 (e.g. 21.8°C = 218)
40035
Read Only
W relay status 0 = Off
1 = Energized
40036
Read Only
Y Relay Status 0 = Off
1 = Energized