http://u-prox.com
24
Program input as 'Door Contact' for proper operation of the door contact.
The control panel can operate without the door contact. In this case, after the
passing RF ID for identify and granting access, an event "Access granted" is
generated, the control panel send unlocking impulse, and returns to normal mode
after door time expire.
Combined Loop- RTE and Door Contact
Panel inputs can be configured for simultaneous use of RTE button and Door
Contact on single loop. In this case the loop breaking means breaking of Door
Contact and (short-circuit) shorted - pressing of RTE button
The example of combined loop connection to Z1 terminals is on the Fig. 17.
Fig 17.
Connecting combined loop
Z1 input function assigned as follows:
Z1 - Combined door contact and RTE of access point A
Any of two inputs can be assigned as a combined for service door contact and RTE
button.
Loop "Control 220 and Battery"
Panel input may be installed to supervise status of power supply. Circuits connected
to panel input, indicate status of external power supply (220V and battery). In Fig. 18
connection of power supply and panel U-Prox IP100 is shown. PWG and ACG can
be open collector outputs or relay outputs (dry contacts) sink to the ground at normal
mains power and battery state respectively.
Fig 18.
Connecting of Control Loop 220 and the battery to power supply
Z2 input function assigned as follows:
Z2 - Control 220 and battery