http://u-prox.com
25
Actuators
Panel has one relay to supervise actuators. Using this output, panel controls electric
lock or latch, operation of the barrier, turnstile, or turns on any optional hardware.
Relay 1 has normally closed and normally open contacts. The relay contacts rating is
1A @ 24 V.
Voltage ripple at actuator operation must not cause the panel malfunction. In case of
such malfunction power up actuators from alternate power supply.
Electric locks
Normally closed and normally open relay contacts, are programmable for a wide
range (0 ... 255 sec) of lock operation time.
Рanel controls electric lock or latch,
barrier operation, turnstile, or turns on and off any optional hardware with this output.
The example of actuator connection is on the Fig. 19. The first is powering the lock
and second by depowering.
Fig 19
. Connecting locks
When using relay to turn on / off current via inductive load, for example, to run
electromagnetic lock, there are electric pulses of high amplitude. To prevent damage
of relay contacts shunt inductive load by diode, set in opposite direction to voltage of
coil supply
Remember, that low-cost solenoid latch do not allow long power supply. For these
latches program the lock time as short as possible to prevent coil overheating.
Assign relay outputs as outputs of locks at panel programming for proper operation.
When the lock time is equal to 0 pulse duration of 200 ms will sent to relay.
Do not use diodes for connecting actuators to AC power supply.