Appendix C – Table of MFC710 frequency converter's parameters
Parameter / Name
Function
Available options / measurement unit
Factory
setting
Change
during
operation
3.4 I therm.0
Setting of thermorelay for
stopped motor
0.0 ... 200.0 %
50.0 %
YES
3.5 therm.Const
Constant of motor heating
0 ... 200 min.
depends on
the nominal
power of the
converter
YES
3.6 Energy Reset
Resetting energy counter
000 NO –
not active
001 YES –
reset energy counter (par. 0.13)
000 NO
YES
3.10 Ext. fail.1
Choice of external failure
source 1
000 Sw.Off –
disabled
001 In.C1 … 006 In.C6 –
reporting external failure 1,
when there is voltage supplied on digital input
DI1..DI6
003 In.C3
YES
3.11 Ext. fail.2
Choice of external failure
source 2
000 Sw.Off –
disabled
001 In.C1 … 006 In.C6 –
reporting external failure 2,
when there is voltage supplied on digital input
DI1..DI6
000 Sw.Off
YES
3.12
Level Ext. 1
Determination of the state
that activates an external
failure 1 (par. 3.10)
0 - low state of selected digital input
in parameter 3.10 activates
external failure 1
1 - high state of selected digital input
in parameter 3.10 activates fault
external 1
The parameter is available from software version
12.63.
1
YES
3.13
Level Ext. 2
Determination of the state
that activates an external
failure 2 (par. 3.11)
0 - low state of selected digital input
in parameter 3.11 activates
external failure 2
1 - high state of selected digital input
in parameter 3.11 activates fault
external 2
The parameter is available from software version
12.63.
1
YES
3.20 Sw.on In.A
Reporting failure of lack of
signal (<2V) when AI
doesn't serve as
referencing-unit
000 Sw.Off –
don't report failures
001 In.C1 … 006 In.C6 –
reporting failures, when
there is voltage supplied on digital input DI1..DI6
007 Sw.On –
always report failures
000 Sw.Off
YES
3.23 Re.4mA lack
Reaction to lack of analog
signal (level <2V (4mA))
000 None
– no reaction
001 Warning –
a warning will be displayed
002 Failure –
device will stop and message will be
displayed
003 Last freq. –
a warning will be displayed,
frequency will stay on an average level from last 10 s
004 Const freq. 7
–
device keeps working with
frequency f const 7 (par. 2.39)
001 Warning
YES
3.30 Re.Sym. lack
Reaction to asymmetry of
the load
000 None –
no reaction
001 Warning –
a warning will be displayed
002 Failure
– device will stop and message will be
displayed
002 Failure
YES
3.35 I ground
Value of leakage current at
which device will be shut
down
0.0 ... 100.0 % In of the motor
25.0 %
YES
3.40 Stall Re.
Reaction to stall of the
motor
000 None –
no reaction
001 Warning –
a warning will be displayed
002 Failure
– device will stop and message will be
displayed
000 None
YES
3.41 f Stall
Stall frequency
0.0 ... 50.0 Hz
10.0 Hz
YES
3.42 Stall time
Stall time
0 ... 600 s
120s
YES
3.45 Spd. err Re.
Reaction to error of output
speed
000 None –
no reaction
001 Warning –
a warning will be displayed
002 Failure
– device will stop and message will be
displayed
000 None
YES
3.46 Delta n-nz
Acceptable difference
between referenced speed
and speed of the motor.
0 ... 1000 rpm
200 rpm
YES
3.47 D time max.
Maximum time of
acceptable error
0.0 ... 12.0 s
0.1 s
YES
3.50 Re. Underl.
Reaction to underload
000 None
– no reaction
001 Warning –
a warning will be displayed
002 Failure
– device will stop and message will be
displayed
000 None
YES