Part Two
60
Flow Station Pressure Transducer Zero
NOTE
: Not required for linear flow stations with 0-10 VDC output.
Pressure based flow station
Disconnect tubing between pressure transducer and flow station.
Enter menu that corresponds to flow station: Supply Flow, Exhaust Flow, or Hood Flow.
Select
SP# FLO ZERO
to take a supply flow station zero.
or
Select
EX# FLO ZERO
to take a general exhaust flow station zero.
or
Select
HD# FLO ZERO
to take a fume hood flow station zero.
Press
SELECT
key. Flow zero procedure, which takes 10 seconds, is automatic.
Press
SELECT
key to save data.
Connect tubing between pressure transducer and flow station.
NOTE
: #; insert number of flow station you are performing a zero on.
Linear flow station 1-5 VDC output
Remove flow station from duct, or cutoff flow in duct. Flow station must have no flow
going past the sensor.
Enter menu that corresponds to flow station location: Supply Flow, Exhaust Flow, or
Hood Flow.
Select
SP# FLO ZERO
to take a supply flow station zero.
or
Select
EX# FLO ZERO
to take a general exhaust flow station zero.
or
Select
HD# FLO ZERO
to take a fume hood flow station zero.
Press
SELECT
key. Flow zero procedure, which takes 10 seconds, is automatic.
Press
SELECT
key to save data.
Install flow station back in duct.
NOTE
: #; insert number of flow station you are performing a zero on.
2-Point Flow Calibration
Supply and General Exhaust Flow Calibration:
Enter menu that corresponds to flow calibration: Supply Flow, Exhaust Flow.
Select
SP LOW SETP
to enter a supply flow low calibration set point.
or
Select
EX LOW SETP
to enter a general exhaust flow low calibration set point.
The DIM will display a value between 0% OPEN and 100% OPEN. Press the
S
or
T
keys to adjust the value displayed (and the damper position). Using a voltmeter, read the
input voltage from the appropriate pressure transducer. When the voltmeter reading is
approximately 20% of the full flow reading (100% OPEN) press the
SELECT
key to
save the data.
then