CONFIGURE MENU
MENU ITEM
SOFTWARE
NAME ITEM
DESCRIPTION
ITEM RANGE
DEFAULT
VALUE
DISPLAY UNITS
UNITS
The
UNITS
item selects the unit of measure that the DIM
displays all values (except calibration span). These units display
for all menu items set points, alarms, flows, etc.
FT/MIN, m/s, in. H
2
O
Pa
"H
2
O
GENERAL
EXHAUST DUCT
CONFIGURATION
EXH
CONFIG
The
EXH CONFIG
menu item determines the exhaust
configuration. If the general exhaust duct is separate from the
total exhaust select
UNGANGED
(left side of Figure 6). If the
general exhaust duct is part of the total exhaust select
GANGED
(right side of Figure 6). The correct configuration is
required for the control algorithm to function correctly.
Figure 6: Exhaust Configuration
NOTE
: In either the GANGED or UNGANGED configuration
a general exhaust flow measurement is required.
UNGANGED or
GANGED
UNGANGED
ACCESS
CODES
The
ACCESS CODES
item selects whether an access code
(pass code) is required to enter any menu. The
ACCESS
CODES
item prevents unauthorized access to a menu. If
ACCESS CODES
is ON, a code is required before the menu
can be entered. Conversely, if
ACCESS CODES
is OFF, no
code is required to enter the menu.
ON or OFF
OFF
END
OF
MENU
The
END OF MENU
item informs you that the end of a menu
has been reached. You can either scroll back up the menu to
make changes, or press the
SELECT
or
MENU
key to exit out
of the menu.