28
Part Two
CONTROL MENU
(continued)
MENU ITEM
SOFTWARE
NAME ITEM
DESCRIPTION
ITEM RANGE
DEFAULT
VALUE
TEMPERATURE
THROTTLING
RANGE
TEMP TR
The
TEMP TR
item determines the controller’s temperature
control throttling range, which is defined as the temperature
range for the controller to fully open and fully close the reheat
valve.
0
10
20
30
40
50
60
70
80
90
100
110
64
65
66
67
68
69
70
71
72
73
74
75
76
Temperature (F)
% O
p
en
6F Throttling
Range
If
TEMP
TR
is set to 3.0
°
F, and the
TEMP SETP
is set to
70.0
°
F, the reheat valve will be fully open when the space
temperature is 67
°
F. Similarly, the reheat valve will be fully
closed when the space temperature is 73.0
°
F.
2.0
°
F to 20.0
°
F
6.0
°
F