36
Part Two
DIAGNOSTICS MENU
(continued)
MENU ITEM
SOFTWARE
NAME ITEM
DESCRIPTION
REM SET POINT
INPUT
REMOTE
SWT
The
REMOTE SWT
item reads the input of the
REMOTE SWT
contact pins 3 and 4. When this item is entered,
the display will indicate either open or closed. If the display indicates open, the AOC uses the
SET POINT
pressure set point. If the display indicates closed, the AOC uses the
REM SET POINT
pressure set point.
RELAY OUTPUT
LOW ALM
REL
HIGH ALM
REL
LOW SUP
REL
HIGH SUP
REL
The relay menu items are used to change the state of a particular relay contact:
LOW, HIGH, LOW SUP, HIGH
SUP
. When an item is entered, the display will indicate either
OPEN
or
CLOSED
. The
S
/
T
keys are used to
toggle the state of the relay. Pressing the
S
key will
OPEN
the alarm contact. Pressing the
T
key will
CLOSE
the
alarm contact. When the contact is closed, the relay is in an alarm condition.
PRESSURE
ANALOG OUTPUT
PRESS
AOUT
The
PRESS AOUT
item is used to verify the analog outputs are working. When this item is entered, the number
shown on the display indicates the last analog output value. The value displayed ranges from 0 to 255. The value
255 corresponds to 0 volts (4 mA) output and 0 corresponds to 10 volts (20 mA) output. Pressing the
S
/
T
keys
change the count on the display. Pressing the
S
key should increase the analog output. Pressing the
T
key will
decrease the analog output.
The
PRESS AOUT
function used in conjunction with a volt meter will verify the individual analog output is
operating correctly.
SUPPLY ANALOG
OUTPUT
SUPPLY
AOUT
The
SUPPLY AOUT
item is used to verify the analog outputs are working. When this item is entered, the number
shown on the display indicates the last analog output value. The value displayed ranges from 0 to 255. The value
255 corresponds to 0 volts (4 mA) output and 0 corresponds to 10 volts (20 mA) output. Pressing the
S
/
T
keys
change the count on the display. Pressing the
S
key should increase the analog output. Pressing the
T
key will
decrease the analog output.
The
SUPPLY AOUT
function used in conjunction with a volt meter will verify the individual analog output is
operating correctly.