![TSI Instruments SUREFLOW 8682 Operation And Service Manual Download Page 82](http://html1.mh-extra.com/html/tsi-instruments/sureflow-8682/sureflow-8682_operation-and-service-manual_1178123082.webp)
76
Appendix B
8682 Modbus Variable List
Variable Name
Variable
Address
Input Provided to Master System
Integer DDC system
receives
Software Version
0
Current Software Version
1.00 = 100
Controller Type
1
Controller Model Number
8682
Emergency Mode
2
Emergency Mode Control
0 Leave emergency mode
1 Enter emergency mode
Control Mode
3
Control mode of device.
0 Normal
1 Unoccupied (Setback)
Status Index
4
Status of S
URE
F
LOW
device 0
Normal
1 Dim Data Error
2 Alarm = Low Pressure
3 Alarm = High Pressure
4 Alarm = Min Supply
5 Alarm = Max Exhaust
6 Data
Error
7 Cal
Error
8 Emergency
Mode
Room Velocity
5
Velocity of room pressure
Displayed in ft/min.
Room Pressure
6
Room Pressure
Displayed in inches H2O.
Host DDC system must
divide by 100,000 to report
pressure correctly
Total Supply Flow
7
Total supply into laboratory
Displayed in CFM.
Total Exhaust Flow
8
Total exhaust out of laboratory
Displayed in CFM.
Offset Set point
9
Current offset set point
Displayed in CFM.
Temperature
10
Current temperature value
Displayed in
°
F.
Fume Hood 1 Flow
11
Flow measured by flow station
connected to hood input #1.
Displayed in CFM.
Fume Hood 2 Flow
12
Flow measured by flow station
connected to hood input #2.
Displayed in CFM.
Fume Hood 3 Flow
13
Flow measured by flow station
connected to hood input #3.
Displayed in CFM.
Fume Hood 4 Flow
14
Flow measured by flow station
connected to hood input #4.
Displayed in CFM.
Fume Hood 5 Flow
15
Flow measured by flow station
connected to hood input #5.
Displayed in CFM.
Fume Hood 6 Flow
16
Flow measured by flow station
connected to hood input #6.
Displayed in CFM.
Fume Hood 7 Flow
17
Flow measured by flow station
connected to hood input #7.
Displayed in CFM.
Exhaust 1 Flow
18
Flow measured by flow station
connected to general exhaust input #1.
Displayed in CFM.
Exhaust 2 Flow
19
Flow measured by flow station
connected to general exhaust input #2.
Displayed in CFM.
Supply 1 Flow
20
Flow measured by flow station
connected to supply flow input #1
Displayed in CFM.
Supply 2 Flow
21
Flow measured by flow station
connected to supply flow input #2
Displayed in CFM.
Supply 3 Flow
22
Flow measured by flow station
connected to supply flow input #3
Displayed in CFM.
Supply 4 Flow
23
Flow measured by flow station
connected to supply flow input #4
Displayed in CFM.