24
Part Two
CONTROL MENU
(continued)
MENU ITEM
SOFTWARE
NAME ITEM
DESCRIPTION
ITEM RANGE
DEFAULT
VALUE
CONTROL SIGNAL
CONTROL
SIG
The
CONTROL SIG
item switches both the supply and exhaust
control outputs from 0–10 VDC to 4–20 mA.
TSI actuators require a 0-10 VDC control signal.
4–20 mA or 0–10 VDC
0-10 VDC
SUPPLY CONTROL
DIRECTION
SUP CONT
DIR
The
SUP CONT SIG
item determines the supply control
signal’s output direction. As an example; if the control system
closes the supply damper instead of opening the damper, this
option will reverse the control signal to now open the damper.
Direct or Reverse
Direct
EXHAUST
CONTROL
DIRECTION
EXH CONT
DIR
The
EXH CONT SIG
item determines the exhaust control
signal’s output direction. As an example; if the control system
closes the exhaust damper instead of opening the damper, this
option will reverse the control signal to now open the damper.
Direct or Reverse
Direct
TEMPERATURE
CONTROL
DIRECTION
TEMP DIR
The
TEMP CONT SIG
item determines the temperature
control signal’s output direction. As an example; if the control
system closes the reheat valve instead of opening the valve, this
option will reverse the control signal to now open the valve.
Direct or Reverse
Direct
REHEAT CONTROL
SIGNAL
REHEAT SIG
The
REHEAT SIG
item switches the temperature control
output from 0–10 VDC to 4–20 mA.
4–20 mA or 0–10 VDC
0-10 VDC