Technical Section
69
Symptom
Possible Cause
Corrective Action
Control system is
not controlling
(continued
)
Damper is full open
or full closed, won’t
move.
Actuator jumper is missing or loose. Verify jumper is installed
correctly.
Control wires are loose. Check wires and verify control output is
working (see
no control output signal).
If control output test passes,
verify damper is rotating correct direction (see
damper rotating
opposite direction).
If damper is rotating correctly and set point cannot
be reached, DIM will fully rotate damper to get as close to set point as
possible. Air balance needs to be adjusted.
Sensor does not
calibrate.
Sensor
communications not
working.
Check
SENSOR STAT
item in diagnostics menu. If
NORMAL
is
displayed, sensor is okay, if
COMM ERROR
is displayed, check
wiring, pressure sensor address, and that DIP switch 1 & 2 are ON
(Figure 10).
Figure 10: Pressure Sensor DIP Switch
Incorrect
pressure
sensor address.
Pressure sensor must have address of 1. Check pressure sensor DIP
switches 5 & 6 and verify address 1 is correct
(7-12 must be OFF).
Pressure sensor red
LED is blinking
(Figure 8).
Problem with sensor
(slow uniform blink).
Communication (fast
burst of non-uniform
blinking).
Red LED is
constantly on.
Check
SENSOR STAT
and confirm
NORMAL
is displayed. If
ERROR
is displayed, correct error.
Unit is communicating with DIM. This is normal.
This is normal when no problems exist or when no communication is
occurring.