SYSTEM FLOW MENU
(continued)
MENU ITEM
SOFTWARE
NAME ITEM
DESCRIPTION
ITEM RANGE
DEFAULT
VALUE
GENERAL
EXHAUST FLOW
SET POINT
(CALCULATED)
EXH SET
POINT
The
EXH SET POINT
menu item displays the general exhaust
flow set point, which is calculated by the AOC control
algorithm. The
EXH SET POINT
is a diagnostic item used to
compare the actual
EX1 FLOW IN
and
EX2 FLOW IN
to the
calculated flow (they should match within 10%). This is a
system information only menu item; no programming is
possible.
NONE: Read only
value
NONE
END
OF
MENU