Part Two
INPUT CHECK MENU
MENU ITEM
SOFTWARE
NAME ITEM
DESCRIPTION
ITEM RANGE
DEFAULT
VALUE
INDIVIDUAL
SUPPLY FLOW
SIGNAL CHECK
SUP 1
through
SUP 4
When one of these items is entered, a voltage, representing the
corresponding flow input, will be displayed. If the voltage
displayed is negative, double check the polarity of the flow
input wiring.
NONE: Read only
value
NONE
INDIVIDUAL
EXHAUST FLOW
SIGNAL CHECK
EXH 1
and
EXH 2
When one of these items is entered, a voltage, representing the
corresponding flow input, will be displayed. If the voltage
displayed is negative, double check the polarity of the flow
input wiring.
NONE: Read only
value
NONE
INDIVIDUAL
FUME HOOD
EXAUST FLOW
SIGNAL CHECK
HOOD 1
through
HOOD 7
When one of these items is entered, a voltage, representing the
corresponding flow input, will be displayed. If the voltage
displayed is negative, double check the polarity of the flow
input wiring.
NONE: Read only
value
NONE
END
OF
MENU
The
END OF MENU
item informs you that the end of a menu
has been reached. You can either scroll back up the menu to
make changes, or press the
SELECT
or
MENU
key to exit out
of the menu.