86
Appendix B
Model 8682-BAC BACnet MS/TP Object Set
Object Type
Device
Instance *Units
Description
Analog Input
1
ft/min, m/s,
in. H
2
O, Pa
Room Pressure
Analog Input
2
cfm, l/s
Total Supply Flow
Analog Input
3 cfm,
l/s
Total General Exhaust
Flow
Analog Input
4
cfm, l/s
Total Hood Flow
Analog Input
5
cfm, l/s
Total Exhaust Flow
Analog Input
6
cfm, l/s
Supply 1 Flow Rate
Analog Input
7
cfm, l/s
Supply 2 Flow Rate
Analog Input
8
cfm, l/s
Supply 3 Flow Rate
Analog Input
9
cfm, l/s
Supply 4 Flow Rate
Analog Input
10
cfm, l/s
Exhaust 1 Flow Rate
Analog Input
11
cfm, l/s
Exhaust 2 Flow Rate
Analog Input
12
cfm, l/s
Hood 1 Flow Rate
Analog Input
13
cfm, l/s
Hood 2 Flow Rate
Analog Input
14
cfm, l/s
Hood 3 Flow Rate
Analog Input
15
cfm, l/s
Hood 4 Flow Rate
Analog Input
16
cfm, l/s
Hood 5 Flow Rate
Analog Input
17
cfm, l/s
Hood 6 Flow Rate
Analog Input
18
cfm, l/s
Hood 7 Flow Rate
Analog Input
19
cfm, l/s
Supply Flow Set Point
Analog Input
20 cfm,
l/s
General Exhaust Flow Set
Point
Analog Input
21
cfm, l/s
Current Flow Offset
Analog Input
22
°F, °C
Temperature
Analog Input
23
% Open
Supply Damper Position
Analog Input
24
% Open
Exhaust Damper Position
Analog Input
25
% Open
Reheat Valve Position
Analog Value
1
MAC Address
1 to 127
Analog Value
2
ft/min, m/s,
in. H
2
O, Pa
Room Pressure Set Point
-0.19500 to 0.19500
in. H
2
O
Analog Value
3
ft/min, m/s,
in. H
2
O, Pa
Remote Pressure Set Point
-0.19500 to 0.19500
in. H
2
O
Analog Value
4
ft/min, m/s,
in. H
2
O, Pa
Low Pressure Alarm
-0.19500 to 0.19500
in. H
2
O
Analog Value
5
ft/min, m/s,
in. H
2
O, Pa
High Pressure Alarm
-0.19500 to 0.19500
in. H
2
O
Analog Value
6
ft/min, m/s,
in. H
2
O, Pa
Remote Low Pressure
Alarm
-0.19500 to 0.19500
in. H
2
O
Analog Value
7
ft/min, m/s,
in. H
2
O, Pa
Remote High Pressure
Alarm
-0.19500 to 0.19500
in. H
2
O
Analog Value
8
cfm, l/s
Vent Min Set Point
0 to 30,000 cfm
Analog Value
9
cfm, l/s
Cooling Flow Set Point
0 to 30,000 cfm
Analog Value
10
cfm, l/s
Unocc Flow Set Point
0 to 30,000 cfm
Analog Value
11
cfm, l/s
Min Offset
0 to 30,000 cfm
Analog Value
12
cfm, l/s
Max Offset
0 to 30,000 cfm
Analog Value
13
cfm, l/s
Max Supply Set Point
0 to 30,000 cfm
Analog Value
14
cfm, l/s
Min Exhaust Set Point
0 to 30,000 cfm