23
4. Operation
06: Voltage Range for ECO Mode
Interface
Setting
Parameter 2:
Low voltage point in ECO Mode. The setting range is from -5% to -10% of the
nominal voltage.
Parameter 3:
High voltage point in ECO Mode. The setting range is from +5% to +10% of the
nominal voltage.
07: Frequency Range for ECO Mode
Interface
Setting
Parameter 2:
Set the low frequency point for ECO Mode.
50 Hz system: Setting range is from 46.0 Hz to 48.0 Hz.
60 Hz system: Setting range is from 56.0 Hz to 58.0 Hz.
The default value is 48.0 Hz/58.0 Hz.
Parameter 3:
Set high frequency point for ECO Mode.
50 Hz: Setting range is from 52.0 Hz to 54.0 Hz.
60 Hz: Setting range is from 62.0 Hz to 64.0 Hz.
The default value is 52.0 Hz/62.0 Hz.
08: Bypass Mode Setting
Interface
Setting
Parameter 2:
OPN:
Bypass allowed. When selected, the UPS will run in Bypass Mode depending on whether the
bypass setting is enabled/disabled.
FBD:
Bypass not allowed. When selected, Bypass Mode is not allowed in any situation.
Parameter 3:
ENA:
Bypass enabled. When selected, Bypass Mode is activated (Default).
DIS:
Bypass disabled. When selected, automatic bypass is acceptable, but manual bypass is
not allowed. Manual bypass means users manually operate UPS for Bypass Mode. For example,
pressing OFF button in AC Mode to turn into Bypass Mode.
09: Maximum Battery Discharge Time Setting
Interface
Setting
Parameter 3:
000~999:
Set the maximum discharge time from 0 to 999 min. The UPS will shut down to the
protect battery if the discharge time arrives before the battery is under voltage. The default value is
990 min.
DIS:
Disable battery discharge protection and backup time will depend on battery capacity.
10: Reserved
Interface
Setting
Reserve for future options.
Summary of Contents for S3M30KX
Page 125: ...125 2 4 2 5 2 6 2 7 TN 4 2 EN IEC 62040 1...
Page 129: ...129 3 3 2 1 1 3 1 2 3 2 3 5 3 1 3 2...
Page 132: ...132 3 OFF R S T N 3 4 3 7 1 2 3 5 3 R S T N R S T N 4 5 6 7 8 S3M30KX S3M40KX 2 1...
Page 135: ...135 4 H M S Fault Warning 4 9 4 11 VAC VDC Hz 0 25 26 50 51 75 76 100 ECO...
Page 147: ...147 4 2...
Page 148: ...148 ECO ECO 4...
Page 149: ...149 4 CVCF CF 50 60 4...
Page 150: ...150 2 CVCF Test 0 5 I P 4...
Page 151: ...151 4 3 4 11 4 9...
Page 155: ...155 6 EPO EPO OFF EPO 43 14 15 16 17 18 19 7 02 4 7 3 CHE Enter CHE Enter L2 L3 L2 L3...
Page 156: ...156 7 7 1 40 C 90 6 24 24 3 7 2 BUS 7 3 Tripp Lite S3MX 1 0 40 C 2 25 C 3 24 7 4 Tripp Lite...