8. Specifications
MODELS
S3M30KX
S3M40KX
S3M60KX
S3M80KX
Capacity (VA)
30 kVA
40 kVA
60 kVA
80 kVA
Capacity (Watts)
27 kW
36 kW
54 kW
72 kW
INPUT
Nominal Voltage
Ph-Ph 380V/400V/415V (Ph-N 220V/230V/240V)
Voltage Range
Ph-Ph 208-478V at < 50% Load; Ph-Ph 208-478V to 305-478V at 50% to 80% Load
(Voltage Range Varies with Load); Ph-Ph 305-478V at > 80% Load
Voltage Comeback
Low-Loss V10V; High-Loss Voltage -10V
Nominal Frequency
50/60 Hz (Auto-Selectable)
Frequency Range
46-54 Hz (50 Hz System); 56-64 Hz (60 Hz System)
Phase
3-Phase with Neutral (3-Phase, N Ground)
Power Factor (100% Load)
≥
0,99
Harmonic Distortion (THDi; 100% Load)
< 3%
OUTPUT
Phase
3-Phase with Neutral (3-Phase, N Ground)
Nominal Voltage
Ph-Ph 380V/400V/415V (Ph-N 220V/230V/240V)
AC Voltage Regulation
(Double-Conversion Mode)
±1% (Balanced Load)
AC Voltage Regulation
(Converter Mode or Battery Mode)
±1%
Power Factor
0,9
AC Voltage Regulation (ECO Mode)
± 11V of Nominal
Frequency
46-54 Hz (50 Hz System); 56-64 Hz (60 Hz System)
Frequency Regulation
(Converter Mode or Battery Mode)
± 0,1 Hz
Frequency Range (Battery Mode)
50 Hz ± 0,1 Hz or 60 Hz ± 0,1 Hz
Overload (AC Mode)
Up to 110% = 10 min; Up to 130% = 1 min; > 130% = 1 s
Overload (Battery Mode)
Up to 110% = 30 s; Up to 130% = 10 s; > 130% = 1 s
Current Crest Ratio
3:1 Maximum
Harmonic Distortion (100% Load)
≤
2% THD (Linear Load);
≤
4% THD (Non-Linear Load)
Transfer Time (Line ‹—› Battery)
0 ms
Transfer Time (Inverter ‹—› Bypass)
Synchronous = 0 ms; Asynchronous < 4 ms
Transfer Time (Inverter ‹—› ECO)
< 10 ms
BYPASS INPUT
Nominal Voltage
Ph-Ph 380V/400V/415V
Phase
3-Phase with Neutral (3-Phase, N Ground)
Voltage Range
Upper Limit: Ph-N 231-264V
Lower Limit: Ph-N 176-209V
Nominal Frequency
50/60 Hz (Auto-Selectable)
Frequency Range
Selectable: ± 1-4 Hz (Default: ± 4 Hz)
Overload (Bypass Mode)
< 150% = 1 min
EFFICIENCY
AC Line Mode
94% at 100% Resistive Load; 93,5% at 50% Resistive Load
ECO Mode
98%, at 100% Resistive Load; 97,5% at 50% Resistive Load
Battery Mode
93,5% at 100% Resistive Load; 93% at 50% Resistive Load
PARALLEL
Parallel for Capacity
Up to 3 Units
Parallel for Redundancy
N/A
INTERNAL BATTERIES (S3M30KX and S3M40KX include internal batteries. Versions are also available without internal
batteries: S3M30KX-NIB and S3M40KX-NIB.)
Type
12V Non-Spillable VRLA AGM/GEL
No Internal Batteries
External Batteries Required for
S3M30KX-NIB, S3M40KX-NIB,
S3M60KX, S3M80KX, S3M100KX,
S3M120KX, S3M160KX and S3M200KX
Capacity
9 Ah
10 Ah
Quantity
80 (2 x Strings of 20 + 20)
Runtime (50% / 100% Load)
17/5.7 min
15/5 min
Recharge Time
9 h to 90%
Maximum Charging Current
2A ± 10%
Float Voltage
13,65V/Battery; 2,27V/Cell
Boost Charging
14,1V/Battery; 2,35V/Cell
End of Discharge
10V/Battery; 1,67V/Cell
Summary of Contents for S3M30KX
Page 125: ...125 2 4 2 5 2 6 2 7 TN 4 2 EN IEC 62040 1...
Page 129: ...129 3 3 2 1 1 3 1 2 3 2 3 5 3 1 3 2...
Page 132: ...132 3 OFF R S T N 3 4 3 7 1 2 3 5 3 R S T N R S T N 4 5 6 7 8 S3M30KX S3M40KX 2 1...
Page 135: ...135 4 H M S Fault Warning 4 9 4 11 VAC VDC Hz 0 25 26 50 51 75 76 100 ECO...
Page 147: ...147 4 2...
Page 148: ...148 ECO ECO 4...
Page 149: ...149 4 CVCF CF 50 60 4...
Page 150: ...150 2 CVCF Test 0 5 I P 4...
Page 151: ...151 4 3 4 11 4 9...
Page 155: ...155 6 EPO EPO OFF EPO 43 14 15 16 17 18 19 7 02 4 7 3 CHE Enter CHE Enter L2 L3 L2 L3...
Page 156: ...156 7 7 1 40 C 90 6 24 24 3 7 2 BUS 7 3 Tripp Lite S3MX 1 0 40 C 2 25 C 3 24 7 4 Tripp Lite...