3. Installation and Setup
3) For 30kA and 40kVA units with internal batteries, there are four battery cable points that are disconnected for shipping purposes
(refer to Figures 3.3 and 3.4). These four cables (two on the right side and two on the left side) will need to be reconnected for proper
battery cabinet operation.
Figure 3.3
Figure 3.4
4) Re-Install the top and side panels from Step 2.
5) Re-Install and tighten all screws from Step 1 with a torque of 1 N•m.
3.3 Single UPS Installation
Installation and wiring must be performed in accordance with local electrical codes/regulations and should only be performed by qualified
personnel.
1) Make sure the mains wire and breakers in the building can sustain the rated capacity of the UPS to avoid electric shock or fire hazard.
Note:
Using a wall receptacle as the input power source for the UPS may result in the receptacle burning or being destroyed.
2) Switch off the mains switch in the building prior to installation.
3) Turn off all the connected devices before connecting to the UPS.
4) Prepare the power cables according to
Table 3.1
. Refer to
Table 3.2
for UPS Input Breaker sizes and
Table 3.3
for Battery Cabinet
Batteries and Breaker sizes.
WARNING:
• Before connecting any wires, make sure the AC input and battery power are completely shut off.
Table 3.1 Power Cables
Model
Wiring Specification
Ground
Input (Ph)
Output (Ph)
Neutral
Battery Packs
S3M30KX
8 AWG [8 mm
2
]
8 AWG [8 mm
2
]
4 AWG [21 mm
2
]
N/A, when using only internal batteries
4 AWG [21 mm
2
]
S3M30KX
8 AWG [8 mm
2
]
8 AWG [8 mm
2
]
4 AWG [21 mm
2
]
4 AWG [21 mm
2
], for external battery pack 4 AWG [21 mm
2
]
S3M40KX 6 AWG [13 mm
2
] 6 AWG [13 mm
2
]
4 AWG [21 mm
2
]
N/A, when using only internal batteries
4 AWG [21 mm
2
]
S3M40KX 6 AWG [13 mm
2
] 6 AWG [13 mm
2
]
4 AWG [21 mm
2
]
4 AWG [21 mm
2
], for external battery pack
4 AWG [21 mm
2
]
S3M60KX 4 AWG [21 mm
2
] 4 AWG [21 mm
2
] 1 AWG [42.4 mm
2
]
1 AWG [42.4 mm
2
]
4 AWG [21 mm
2
]
S3M80KX 2 AWG [34 mm
2
] 2 AWG [34 mm
2
] 1/0 AWG [54 mm
2
]
1/0 AWG [54 mm
2
]
2 AWG [34 mm
2
]
Table 3.2 UPS Input Breakers
Model (Agency Number)
Breaker Size
S3M30KX (AG-030)
63A, 3-Pole
S3M40KX (AG-040)
80A, 3-Pole
S3M60KX (AG-060)
150A, 3-Pole
S3M80KX (AG-080)
6 x 30A Fuses/Phase
Battery cables that need to be reconnected
before proper operation of battery cabinet
Right Side
S3M30KX/S3M40KX
Left Side
S3M30KX/S3M40KX
Summary of Contents for S3M30KX
Page 125: ...125 2 4 2 5 2 6 2 7 TN 4 2 EN IEC 62040 1...
Page 129: ...129 3 3 2 1 1 3 1 2 3 2 3 5 3 1 3 2...
Page 132: ...132 3 OFF R S T N 3 4 3 7 1 2 3 5 3 R S T N R S T N 4 5 6 7 8 S3M30KX S3M40KX 2 1...
Page 135: ...135 4 H M S Fault Warning 4 9 4 11 VAC VDC Hz 0 25 26 50 51 75 76 100 ECO...
Page 147: ...147 4 2...
Page 148: ...148 ECO ECO 4...
Page 149: ...149 4 CVCF CF 50 60 4...
Page 150: ...150 2 CVCF Test 0 5 I P 4...
Page 151: ...151 4 3 4 11 4 9...
Page 155: ...155 6 EPO EPO OFF EPO 43 14 15 16 17 18 19 7 02 4 7 3 CHE Enter CHE Enter L2 L3 L2 L3...
Page 156: ...156 7 7 1 40 C 90 6 24 24 3 7 2 BUS 7 3 Tripp Lite S3MX 1 0 40 C 2 25 C 3 24 7 4 Tripp Lite...