4.9 Fault Codes - When Icon is Solid (Not Flashing)
Fault code Fault Event
Icon
Fault Code
Fault Event
Icon
01
Bus start failure
None
42
DSP communication failure
None
02
Bus over
None
43
Overload
03
Bus under
None
46
Incorrect UPS setting
None
04
Bus unbalance
None
47
MCU communication failure
None
06
Converter over current
None
48
Two DSP firmware versions are
incompatible in parallel system
None
11
Inverter soft start failure
None
60
Bypass phase short circuited
12
High inverter voltage
None
61
Bypass SCR short circuited
None
14
Inverter R output (line to neutral) short
circuited
62
Bypass SCR open circuited
None
15
Inverter S output (line to neutral) short
circuited
63
Voltage waveform abnormal in R phase
None
16
Inverter T output (line to neutral) short
circuited
64
Voltage waveform abnormal in S phase
None
17
Inverter R-S output (line to line) short
circuited
65
Voltage waveform abnormal in T phase
None
18
Inverter S-T output (line to line) short
circuited
66
Inverter current sample abnormal
None
19
Inverter T-R output (line to line) short
circuited
67
Bypass O/P short circuited
1A
Inverter A negative power fault
None
68
Bypass O/P line to line short circuited
1B
Inverter B negative power fault
None
69
Inverter SCR short circuited
None
1C
Inverter C negative power fault
None
6C
BUS voltage drops too fast
None
21
Battery SCR short circuited
None
6D
Current sampling error value
None
23
Inverter relay open circuited
None
6E
SPS power error
None
24
Inverter relay short circuited
None
6F
Battery polarity reverse
None
25
Line wiring fault
None
71
PFC IGBT over-current in R phase
None
31
Parallel communication failure
None
72
PFC IGBT over-current in S phase
None
32
Host signal failure
None
73
PFC IGBT over-current in T phase
None
33
Synchronous signal failure
None
74
INV IGBT over-current in R phase
None
34
Synchronous trigger signal failure
None
75
INV IGBT over-current in S phase
None
35
Parallel communication loss
None
76
INV IGBT over-current in T phase
None
36
Parallel output current unbalance
None
41
Over temperature
None
4. Operation
Summary of Contents for S3M30KX
Page 125: ...125 2 4 2 5 2 6 2 7 TN 4 2 EN IEC 62040 1...
Page 129: ...129 3 3 2 1 1 3 1 2 3 2 3 5 3 1 3 2...
Page 132: ...132 3 OFF R S T N 3 4 3 7 1 2 3 5 3 R S T N R S T N 4 5 6 7 8 S3M30KX S3M40KX 2 1...
Page 135: ...135 4 H M S Fault Warning 4 9 4 11 VAC VDC Hz 0 25 26 50 51 75 76 100 ECO...
Page 147: ...147 4 2...
Page 148: ...148 ECO ECO 4...
Page 149: ...149 4 CVCF CF 50 60 4...
Page 150: ...150 2 CVCF Test 0 5 I P 4...
Page 151: ...151 4 3 4 11 4 9...
Page 155: ...155 6 EPO EPO OFF EPO 43 14 15 16 17 18 19 7 02 4 7 3 CHE Enter CHE Enter L2 L3 L2 L3...
Page 156: ...156 7 7 1 40 C 90 6 24 24 3 7 2 BUS 7 3 Tripp Lite S3MX 1 0 40 C 2 25 C 3 24 7 4 Tripp Lite...