Leaving Water Temperature Control
Setpoints
Table 9 identifies the maximum differential-to-stop and start
settings recommended for the leaving water temperature
(Leaving Water Temperature) setpoints, without violating
the LCWTC or LRTC factory settings. Even though the clear
language display (CLD) differential-to-stop can be set up to
10°F, the following table identifies the maximum setting to
avoid overlap of the evaporator limit and/or low chilled
water temperature cutout.
Figure 30 is a composite of all the settings regarding
leaving water temperature (LWT) control. Depending on
where the actual leaving water temperature falls within the
figure below, will indicate the active UCP2 control functions.
Table 9. Maximum differential start and stop settings for leaving water temperature setpoints
LWT
STPT
40°F
41°F
42°F
43°F
44°F
45°F
46°F
47°F
48°F
49°F
1-10°F
1-10°F
1-10°F
1-10°F
1-10°F
1-10°F
1-10°F
1-10°F
1-10°F
1-10°F
1-1.4°F
1-2.4°F
1-3.4°F
1-4.4°F
1-5.4°F
1-6.4°F
1-7.4°F
1-8.4°F
1-9.4°F
1-10°F
LCWTC
38°F
38°F
38°F
38°F
38°F
38°F
38°F
38°F
38°F
38°F
LRTC
36°F
36°F
36°F
36°F
36°F
36°F
36°F
36°F
36°F
36°F
Differential
to Start
Differential
to Start
In order to increase the differential-to-stop without violating
the LWTC or LRTC, the factory settings of 38°F and 36°F
respectively would need to be altered from within the
password protected service settings, field startup group
menus. As stated previously, they are each adjustable from
35-38°F. The factory settings should not be altered if at all
possible.
Figure 30. Leaving water temperature control settings
Differential to Start
LCWT Setpoint
Differential to Stop
Minimum LCWT via
LCWTC
Minimum LCWT via LRTC
LRT Unload
LTR Hold, and LCWTC 38
LTR Unload
LRTC