The following displays appear as the next key is pressed to
advance through the menu.
The displays are self explanatory except as noted. Some
displays are present only when the option is selected. In
some cases options are user selectable, others are factory
selected per order.
3. Active Priority Setpoint-Heat or Cool Priority Setpoint
Source Setpoint
(only with Auxiliary Heating option is
installed)
Priority
Status 1
(settings source) Priority:
Status 2
The unit can be selected as cooling only, heating only,
cooling priority, and heating priority. The following display
identifies the active priority AND where the priority
selection originated.
•
Status 1 and 2 will be one of the following: 1) Cooling
Only, 2) Heating Only, 3) Cooling Priority, 4) Heating
Priority
•
Settings source will be one of the following: 1) Front
Panel, 2) External, 3) Tracer
Notes about diagnostics occurring during simultaneous
operation:
•
Diagnostics occurring that effect the priority mode will
shutdown the chiller, and alarm.
•
Diagnostics occurring with the non-priority mode will
cease operation in the non-priority mode and allow
continued operation in the priority mode. To do this, the
control system will change over to the non-
simultaneous mode of operation leaving the priority
mode only in operation. The diagnostic will be tagged
as an informational warning (IFW) type.
These same diagnostics, if occurred in heating or cooling
only mode, would be machine shutdown manual reset
required (MMR), or machine shutdown automatic reset
(MAR) types.
4. Chilled Water Setpoint or Evaporator Leaving Water
Temperature
(unless Heat Only)
Chilled Water Setpoint (Source)
xxx.xf/c
Evaporator Leaving Water Temperature:
xxx.xf/c
If the source is front panel then (Source) will not be
displayed, otherwise (Source) will be one of the following:
External, Tracer, or, Reset
5. Chilled Water Reset Source (when Enabled) Setpoint or
Chilled Water Setting Source Setpoint (Unless Heat Only).
(Source):
CWS xxx.xf/c
(Settings Source):
CWS xxx.xf/c
(Source) will be either: Outdoor Air, Return Reset, or,
Constant Return Reset.
(Settings Source) will be either: Front Panel, External, or
Tracer.
6. Hot Water Setpoint or Evaporator Leaving Water
Temperature
(unless Cool Only)
.
Hot Water Setpoint (Source):
xxx.xf/c
Hot Water Leaving Temperature:
xxx.xf/c
(Source) will be either: Front Panel, External or Tracer.
7. Hot Water Reset Source (when Enabled)
Setpoint/Hot Water Setting Source Setpoint (Unless Cool
Only).
(Source):
HWS xxx.xf/c
(Settings source):
HWS xxx.xf/c
(Source) will be either: Outdoor Air Reset, Return Reset, or
Constant Return Reset.
(Settings source) will be either: Front Panel, External, or
Tracer.
8. (Unless Heating only)
Chilled Water Entering Temperature:
xxxf/c
Chilled Water Leaving Temperature:
xxxf/c
9.
(Only with Auxiliary Heating option installed
and selected).
Hot Water Entering Temperature:
xxx.xf/c
Hot Water Leaving Temperature:
xxx.xf/c
10.
Absorber Entering Water Temperature:
xxx.xf/c
Absorber Leaving Water Temperature:
xxx.xf/c
11.
Condenser Leaving Water Temperature:
xxx.xf/c
Press (Next)(Previous) to Continue
12.
Option
: Chilled Water Flow or Absorber or Condenser
Water Differential Water Sensing Option and devices
installed.
Approximate Chiller Water Flow:
xxxgpm/lps
Approximate Absorber/Condenser Water Flow
xxxgpm/lps
13.
Option
: Only with water flow option installed.
Approximate Chiller Capacity:
xxxxTons
Press (Next)(Previous) to Continue
14
.
Option
: Only with temperature sensor installed (or
Tracer)
Outdoor Air Temperature:
xxxf/c
Press (Next) (Previous) to Continue