Table 7 identifies unit sensors, primary function control or
monitor, connection points and the normal operation
temperature range of the sensors located in the fluid cycle.
Table 7
Figure 13
Module
1
Evaporator Leaving Water Temperature
28 - 70
LCWT Control
Chiller
Design 44
2
Evaporator Entering Water Temperature
28 - 80
LCWT Control
Chiller
Design 54
3
Condenser Leaving Water Temperature
55 - 110
Monitor
Chiller
Design 103
4
Absorber Leaving Water Temperature
45 - 100
Monitor
Chiller
Design 95
5
Absorber Entering Water Temperature
55 - 110
ELWT-Fdfwd &
Chiller
Design 85
Low Tower Limit
6
Entering Heating Hot Water Temperature
120-200
Monitor
Burner
(Used for Simultaneous Heat or Cool)
Design 130-170
7
Leaving Heating Hot Water Temperature
120-200
Monitor
Burner
(Used for Simultaneous Heat or Cool)
Design 140-180
8
120 - 200
Concentration Calc
Stepper
Design 175
(LTG)
9
Saturated Evaporator Refrigerant Temperature
28 - 60
Evaporator Limit
Stepper
Design 38
10
Saturated Condenser Refrigerant Temperature
80 - 180
Concentration Calc
Stepper
Design 100
(LTG)
11
Diff Evaporator Water Pressure
NA
Monitor
TBD
12
Diff Tower Water Pressure
NA
Monitor
TBD
13
Interstage Vapor Pressure Transducer
14.9 - 0 PSIG
Circuit
15
200 - 320
Concentration Calc
Circuit
Design 300
(HTG)
16
Solution Temperature Entering Level Control
120 - 200
Calc Mixed
Circuit
(Before Level Control)
Design 190
Concentration
17
120 -200
Calc Mixed
Circuit
Design 190
Concentration
18
Solution Temperature Entering Absorber
80 - 180
Control T-Margin
Stepper
Design 115
19
Solution Temperature Leaving Absorber
80 - 180
Monitor
Stepper
Design 100
20
120-20
Monitor
Stepper
Design 158
21
Absorber Spray Temperature
80-180
Monitor
Stepper
Design 105
22
200-320
Monitor
Stepper
Design 270
23
High Flue Gas Temperature Cutout
200-350
Circuit
Design 425
24
Sense Detect Recovery (SDR) Temperature
200 - 320
SDR
Circuit
Design 230
Logic
Outdoor Air Temperature (Optional)
-20 - 60
Chiller
Design 80
Sensor
Reference
Usable
Range in °F
Sensor Primary
Function
Temperature
Monitor
Chilled Water
Reset Control
High and Low
Pressure Limit
Solution Temperature Leaving Low Temperature
Generator (LTG)
Solution Temperature Leaving High Temperature
Generator (HTG)
Mixed Solution Temperature Entering Low Temperature
Heat Exchanger (LTHX) (After Split)
Solution Temperature at Low Temperature Generator
(LTG) Sprays
Solution Temperature Entering High Temperature
Generator (HTG)