Typical “Chiller Operation Mode Displays” are
provided in the following table.
(This is not an all-inclusive listing)
Machine
Displayed Message
Condition
(First Line/Second Line)
Reset
Resetting
Stop
Remote Stop
External Unit Stop
Unit Remote Stop
Start
Initializing
Start
Auto
Auto
Waiting for Evaporator Water Flow
Auto
Auto
Auto
Waiting for a Need to Cool
Auto
Auto *
Waiting for a Need to Heat
Auto
Auto *
Waiting for a Need to Cool/Heat
Auto
Waiting for Auxiliary Water Flow *
Start
Start
Starting Solution Pumps
Start
Waiting for Ventilation
Start
Starting - Waiting for Combustion
Start
Starting-Preheating solution
Start
Starting - Pre-heating Solution
Spray Pumps Off
Start
Starting - Pre-heating Solution
Spray Pumps On
Unit is Cooling
Unit is Heating*
Unit is Cooling and Heating *
Unit is Heating and Cooling *
Run Softload
Unit is Running Softloading
* ABDA Only with Heating Option (Shaded)
Local Stop: Cannot be overridden by
any External or Remote Device
Remote Display Stop: Chiller may be
set to Auto by any External or
Remote Device
Remote Run Inhibit from External
Source
Remote Run Inhibit from Tracer
Starting is Inhibited by Staggered
Start Time Remaining: Minute or
Second
Waiting for Tracer Communications
to Establish Operating Status
Starting - Waiting for Absorber/
Condenser Water Flow
Run: Normal Cooling
Only
Run: Normal Heating
Only
Run: Normal Cooling
Priority
Run: Normal Heating
Priority
Unit is Running: Low Interstage
Pressure Limit
Run: Solution Flow
Limited by Low Pressure
Continued from Column 1
Unit is Running:
Unit is Running:
Unit is Running:
Unit is Running:
Unit is Running:
Unit is Running:
Dilution Cycle
Dilution Cycle
Dilution Cycle
Dilution Cycle
Dilution Cycle
Dilution Cycle
Dilution Cycle
Dilution Cycle
Dilution Cycle
Transitioning to Stop
Panic Shutdown
Run: Low Cooling Water
Temperature Limit
Low Absorber or Condenser Temperature Limit
Run: Evaporator Limit
Low Evaporator Refrigerant Temperature Limit
Run: Solution Flow Limited
by High Interstage Press
Limit
High Interstage Pressure Limit
Run: Generator Solution
Temperature Limit
High Generator Solution Temperature Limit
Run: High Exhaust Gas
Temperature Limit
High Exhaust Gas Temperature Limit
Run: Burner Cycled Off
Burner Cycled Off
Run: Crystallization
Sensing Detection and
Recovery
Solution Recovery: Pump Off
Time Remaining: Minute or Second
Run: Crystallization
Sensing Detection and
Recovery
Solution Recovery: Pump Off
Time Remaining: Minute or Second
Dilution Cycle Remaining: Minute or Second
Waiting for a Need to Cool
Dilution Cycle Remaining: Minute or Second
Diagnostic Shutdown Auto
Dilution Cycle Remaining: Minute or Second
Diagnostic Shutdown Stop
Dilution Cycle Remaining: Minute or Second
Local Stop
Dilution Cycle Remaining: Minute or Second
Remote Stop
Dilution Cycle Remaining: Minute or Second
Remove Run Inhibit from External Source
Dilution Cycle Remaining: Minute or Second
Remote Run Inhibit from Tracer
Dilution Cycle Remaining: Minute or Second
Waiting for Absorber or Condenser Flow
Chilled Water Pump Delay Time:
Minute or Second
Stop: Transitioning to Stop
Panic Shutdown Sequence Complete
Press Auto or Stop to Continue
Diagnostic Shutdown Stop
Mode
Diagnostic Shutdown Stop
Diagnostic Shutdown Auto
from Auto Mode
Diagnostic Shutdown Auto