7
Point
Concentration
Temperature
Temperature
%
(°F)
(°C)
1
Absorber Dilute Solution
58
95
35
2
58
180
82
3
Solution Leaving the Low Temperature Generator (LTG)
60
190
88
4
Solution Entering the High Temperature Generator (HTG)
60
300
149
5
Solution Leaving the High Temperature Generator (HTG)
65.5
325
163
6
65.5
240
116
7
63.5
215
102
8
63.5
125
52
9
61.5
112
44
10
–
300
149
11
–
190
88
12
Condensed Refrigerant
–
100
38
13
Evaporator Pump Refrigerant
–
42
6
14
System Chilled Water/Entering
–
54
12
15
System Chilled Water/Leaving
–
44
7
16
Absorber Cooling Water
–
85
29
17
–
93
34
18
–
97
36
19
–
346
174
20
–
346
174
21
Condensate Leaving Machine
–
210
99
Table 1. ABTF machine cooling cycle (See Figure 1)
Lithium Bromide Solution
or Refrigerant Water
Absorber Dilute Solution Entering the Low Temperature
Generator (LTG)
Solution Leaving High Temperature Heat Exchanger
(HTHX) and Flow Control Device
Mixed Solution (Intermediate with Concentrated)
Entering Leaving Temperature Heat Exchanger (LTHX)
Solution Entering Absorber Sump or Spray Pump
Absorber Spray Solution (Mixed with absorber dilute)
Absorber Leaving or Condenser Entering Cooling
Water
Condenser Leaving Cooling Water
Steam Entering Unit and 115 psig
Condensate Leaving Generator or Entering
Condensate Heat Exchanger
High Temperature Generator (HTG) Refrigerant Vapor
Low Temperature Generator (LTG) Refrigerant Vapor