Sequence of Operation
(Notes - Reference Next Page)
Events:
Stop Low Temperature Solution Pump
Stop High Temperature Solution Pump
Stop Absorber Pump
Ventilation Stopped
Chilled Water
Pump off delay
Go to
Time
Line 1
Monitor Strong Solution Temperature Leaving Heating,
If <= 200°F then 3 Minute Dilution Cycle.
If > 200°F then 15 Minute Dilution Cycle
Time Line 3
Dilution Cycle
Local or Remote Stop
Standard
Mode Display:
Sequence of Events: From Running through Dilution Cycle
(No intervening Diagnostics or Software Resets.).
Unit is Running
Unit was Running
For an indeterminate
amount of time.
Open Refrigerant Dump Valve (RDV1) to Dilute Solution
Stop Refrigerant Pump
Stop Condenser Water Pump
Command to Low Energy to Low Fire
and Stop Burner (ABDA)
Command Low Temperature Solution Pump
AFD to 75% of Allowable Speed Range
Dilution
Timer
(See Note 4)
15 Seconds
Post
Purge
(Note 3)
While Running all
Limits are Active
Loss of Power During
This State will Result
in a Unit Start When
Power Returns if There
is a Need to Cool.
If There is no need to
Cool when Power Returns
a Dilution Cycle
Will be initiated.
(See Note 1 and 6) (See Note 7)
Go to
Time
Line 1a
(Previous Page)
Auto
Stop Chilled
Water Pump
Completes Dilution Cycle After Satisfying Load
Sequence of Events: Panic Stop
Stop
Stop
Auto
Chilled Water Pump Off
Condenser Water Pump Off
Solution Pumps Off
Refrigerant Pump Off
Absorber Pump Off
Energy Input Off
Ignore HPC Sensor Failure
Diagnostics.
All Other Diagnostics are
active.
Ventilation Off
Refrigerant Dump Valve
(RDV1) Closed
All Stop Modes
All Running Modes
Operator Hits
Stop Twice
within 5 Seconds
This State May
Only be Exited
by Pressing Stop
or Auto Keys
The Auto or Stop switch is
set to Stop. Unit will Enter
a Dilution Cycle.
The Unit will Not start unless
the Auto key is pressed.
The Auto/Stop switch is
set to Auto. Unit will Enter
a Dilution Cycle.
Operator
Presses
Stop
Operator
Presses
Auto
Events:
Power Off
During AUTO
or Dilution
Cycle
Power On
Time Line 4
Interstage
Pressure
Sensor
Open/Short
Diagnostics
Disabled
See Note 2
(Next Page)
Blank
Reset (Hard)
START
(Previous Page)
Stop Selected or AUTO Differential to Stop Occurs
(Cooling Satisfied)
Standard Mode
Display:
See Note 9
(Next Page)
1 Second