35
Operator
Settings
Service
Settings
Service
Tests
Diagnostics
The Service Settings menu has three submenus within it.
First menu is non-password protected consisting of all of
the settings, feature enables, setpoints etc. While seldom
changed by a user, changes do not seriously affect the
protection or reliability of the chiller.
The other submenus (field startup and machine
configuration) are protected, each with a separate service
level password. These are for changing parameters and
settings regarding field commissioning and fundamental
protection and control of the chiller subsystems (Field
Startup), or for programming of the unit control module
(UCM) as to how the specific chiller was built in the Factory
(Machine Configuration). Once properly set, these menus
should never be changed again without specific knowledge
of the effects of the changes. In rare instances, certain field
problems may be corrected by making changes in these
protected menus but certain aspects of chiller reliability may
be compromised. The main reason for accessibility
is for field commissioning and to allow for the
programming of service replacement modules.
1. Service Setting Group Heading
Service Settings: Basic Setups:
Press (Next) (Previous) to Continue
2. Keypad/Display Lockout
This display appears if the keypad lockout feature is
enabled.
Press (Enter) to Lock Display and Keypad
Password will be required to Unlock
If the Enter key is pressed to lock the keypad, the following
message is displayed, and all further input from the keypad
is ignored, including the Stop key, until the password is
entered. The password is entered by pressing the Previous
and Enter keys at the same time.
*****Display and Keypad are Locked*****
*******Enter Password to Unlock*******
If the keypad is locked and the password is entered, the
display will return to the Chiller Report and display the
current Operating Mode.
3. Language: xxxxxxxx
Press (+) (-) to Change Setting
Selections are: English- Default, Francais, Deutsch, Espanol,
Nippon (AKA Katakana, Use Japanese Characters), Italiano,
Netherlands
4.
Possible values of [Type] are: English- Default, SI
Possible values of [Type] are: English- Default, SI
5. Decimal Places Displayed: (Status)
Press (+) (-) to Change Setting
The choices for Status are: XXX.X- Default or, XXX
6.
Display Menu Headings: (d/e)
Press (+) (-) to Change Setting
Default is Enabled. If disabled, the Menu Headings in each
Menu or Group are removed.
7.
Press (Enter) to Clear the Custom Menu.
When Enter is pushed a two-second message appears as
shown below and then returns to above screen.
Custom Menu has been Cleared
8. Clear Service Log
Press (Enter) to Clear the Service Log
When Enter is pushed a two-second message appears as
shown below and then returns to above screen.
Service Log has been Cleared
9.
Differential to start Setpoint: xxx.xf/c
Press (+)(-) to Change Setting
Range of Values is 1 to 10°F (0.5 to 5.5°C) in increments of 1
or 0.1°F, or °C Default 3°F (1.7°C).
10.
Differential to Stop Setpoint: xxx.x f/c
Press (+)(-) to Change Setting
Range of Values is 1 to 10°F (0.5 to 5.5°C) in increments of 1
or 0.1°F. Default is 5°F (2.8°C).
11 .
Evap Pump Off Delay: xxx Min
Press (+) (-) to Change Setting
Range of Values is 1 to 30 minutes in increments of 1
Minute. Default is 1 Minute.
This is the length of time the evaporator pump will be
instructed to remain on after the dilution cycle terminates.