Check code
[E07] / [–]
(Current code / AI-NET)
Check code name
Indoor/Outdoor
communication circuit error
(Detected at outdoor side)
Cause of operation
1. Indoor/outdoor communication end terminal
resistance setup error
2. Indoor/outdoor communication connection error
Is there noise source?
YES
YES
YES
YES
YES
YES
NO
NO
NO
NO
NO
NO
Is setup of end terminal resistance
of outdoor unit normal?
Is inter-unit cable (U1, U2) between
indoor and outdoor short-circuited?
Is connection of inter-unit cable
between indoor and outdoor correct?
Is there no error on
power cable to outdoor unit?
Is F400 (fuse) on
I/F P.C. board opened?
Outdoor I/F P.C. board failure
→
Replace
Eliminate noise.
Correct power cable.
Correct
communication line.
I/F P.C. board failure
However an emergent operation is
available by inserting connector to
be connected to CN01 to CN33.
Correct short-circuit.
* Check conduction
with tester.
Turn on power to
start operation.
Correct setup of end
terminal resistance.