Check code
[P12] / [11]
(Current code / AI-NET)
Check code name
Indoor fan motor error
Cause of operation
1. Fan motor connector error
2. Fan motor error
3. Indoor P.C. board error
4. Cross-flow fan bearing error
Stop operation andtake off
plug socket.
Remove motor connector,
connect plug socket again,
and then stop the operation
from remote controller.
Stop operation, turn off
breaker, turn on breaker again,
and then stop operation from
remote controller.
Does fan stop under
condition of operation stop?
Does fan rotate?
Turn on breaker after
approx. 10 seconds.
Turn off breaker once.
Is voltage more than DC1V
supplied between
5
+ and
3
–
of motor connector (CN210)?
(Motor connection status)
Is voltage DC15V supplied
between
4
+ and
3
– of
motor connector (CN210)?
Is voltage more than DC 1V supplied
between
5
+ and
3
– of motor connector
(CN210) when turning on the motor
(except heating mode) from remote controller?
(Check it within 15 seconds
after start of operation.)
Does voltage 0 to 15V
(No. of rotation return signal) generate
between
6
+ and
3
– of motor connector
(CN210) when rotating cross-flow fan with
hands under condition of operation stop?
Start cooling operation
with LOW setup
Change setup of
cooling wind to HIGH.
Replace
indoor fan motor.
Repair bearing
of cross-flow fan.
Replace indoor main P.C. board
(MCC-1510).
Fan motor is normal.
Does cross-flow fan
rotate normally with hands?
Is voltage more than DC 1V supplied
between
5
+ and
3
– of motor connector
(CN210) when turning on the motor
(except heating mode) from remote controller?
(Check it within 15 seconds
after start of operation.)
Does rpm of fan increase?
Is voltage more than
DC280V supplied between
4
+ and
3
– of motor
connector (CN210)?
YES
YES
YES
YES
YES
NO
YES
YES
YES
YES
YES
YES
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
Is voltage more than DC280V
supplied between
1
+ and
3
–
of motor connector (CN210)?