50
SMMS High-Wall Type
Installation Manual
Toshiba
11
APPLICABLE CONTROLS
A wired remote controller is necessary for this function. This function cannot be operate with a wireless
remote controller.
REQUIREMENT
• When you use this air conditioner for the first
time, it takes approx. 5 minutes until the remote
controller becomes available after power-on.
This is normal.
<When power is turned on for the first time
after installation>
It takes
approx. 5 minutes
until the remote
controller becomes available.
<When power is turned on for the second (or
later) time>
It takes
approx. 1 minute
until the remote
controller becomes available.
• Normal settings were made when the indoor
unit was shipped from factory.
Change the indoor unit settings as required.
• Use the wired remote controller to change the
settings.
Changing of settings of for
applicable controls
Basic procedure for changing settings
Change the settings while the air conditioner is not
working.
(Be sure to stop the air conditioner before making
settings.)
The display content for setting differs from that on
the former types of remote controller (RBC-
AMT21E/AMT31E). (The number of CODE No. has
increased.)
Procedure
1
Push
button and “TEMP.”
button
simultaneously for at least 4 seconds.
After a while, the display flashes as shown in the
figure.
Confirm that the CODE No. is [10].
• If the CODE No. is not [10], push
button to
erase the display content, and repeat the
procedure from the beginning.
(No operation of the remote controller is
accepted for a while after
button is pushed.)
(While air conditioners are operated under the
group control, “ALL” is displayed first. When
is pushed, the indoor unit number
displayed following “ALL” is the header unit.)
* The settings cannot be changed using the
wireless remote controller, sub remote
controller, or remote-controller less system
(for central remote controller only).
Therefore, install the wired remote controller
to change the settings.
Approx. 5 minutes
Power
on
“SETTING”
flashes
“SETTING”
goes out
Remote
controller is
available
Approx. 1 minutes
Power
on
“SETTING”
flashes
“SETTING”
goes out
Remote
controller is
available
1
6
1
3
2
5
4
(* Display content varies with
the indoor unit model.)
+1111050501_01EN_SMMS_HighWall_IM_B5.book Page 21 Wednesday, November 12, 2008 2:45 PM
SMMS High-Wall Type
Installation Manual
Toshiba
Procedure
2
Each time you push
button, indoor unit
numbers in the control group change cyclically.
Select the indoor unit you want to change settings
for.
The fan of the selected unit runs and the louvers
start swinging. You can confirm the indoor unit for
which you want to change settings.
Procedure
3
Using “TEMP.”
/
buttons, specify CODE
No..[
].
Procedure
4
Using timer “TIME”
/
buttons, select SET
DATA [
].
Procedure
5
Push
button. When the display changes from
flashing to lit, the setup is completed.
• To change settings of another indoor unit, repeat
from Procedure
2
.
• To change other settings of the selected indoor
unit, repeat from Procedure
3
.
Use
button to clear the settings.
To make settings after
button was pushed,
repeat from Procedure
2
.
Procedure
6
When settings have been completed, push
button to determine the settings.
When
button is pushed, “SETTING” flashes and
then the display content disappears and the air
conditioner enters the normal stop mode.
(While “SETTING” is flashing, no operation of the
remote controller is accepted.)
Change of lighting time of filter
sign
According to the installation condition, the lighting
time of the filter sign (Notification of filter cleaning)
can be changed.
Follow to the basic operation procedure
(
1
→
2
→
3
→
4
→
5
→
6
).
• For the CODE No.. in Procedure
3
, specify [01].
• For the [SET DATA] in Procedure
4
, select the
SET DATA of filter sign lighting time from the
following table.
To secure better effect of heating
When it is difficult to obtain satisfactory heating due
to installation place of the indoor unit or structure of
the room, the detection temperature of heating can
be raised. Also use a circulator, etc. to circulate
heat air near the ceiling.
Follow to the basic operation procedure
(
1
→
2
→
3
→
4
→
5
→
6
).
• For the CODE No.. in Procedure
3
, specify [06].
• For the SET DATA in Procedure
4
, select the
SET DATA of shift value of detection
temperature to be set up from the table below.
SET DATA
Filter sign lighting time
0000
None
0001
150H (Factory setting)
0002
2500H
0003
5000H
0004
10000H
SET DATA
Detection temp shift value
0000
No shift
0001
+1°C
0002
+2°C
0003
+3°C (Factory setting)
0004
+4°C
0005
+5°C
0006
+6°C