Check code
[H06] / [20]
(Current code / AI-NET)
Check code name
Low-pressure
protective operation
Cause of operation
1. Service valve close
2. Ps sensor error
3. SV2, SV4 circuit error
4. Miscabling of communication between indoor
and outdoor
5. Indoor/outdoor fan and condenser error
6. Indoor/outdoor PMV clogging
7. Indoor/outdoor heat exchanger clogging
8. Refrigerant shortage
Is there clogging on whole valve?
Is outdoor fan normally
operated in heating season?
* 1 Pressure by pressure gauge (Check joint)
2 Pressure display on 7-segment display
3 Output voltage of I/F P.C. board
If 1 and 2, 3 are different, an error of pressure sensor error is considered.
If 2 and 3 are different, check I/F P.C. board.
Check miscabling, misinstallation and
connector connection.
(Check with miscabling check function of outdoor unit.)
YES
YES
YES
YES
YES
YES
NO
YES
YES
YES
YES
YES
YES
YES
NO
NO
NO
NO
NO
NO
YES
NO
NO
NO
NO
NO
NO
NO
Open service valves fully.
Exchange low-pressure sensor.
Correct SV2 and SV4 circuits.
Correct cabling.
Are SV2 and SV4 circuits normal?
Are service valves of gas and
liquid pipe of outdoor unit fully opened?
Is not indoor unit with
different circuit connected?
In cooling season, go to (A)
In heating season, go to (B)
Does indoor fan normally
operate in cooling season?
Are characteristics of
low-pressure sensor normal?
Is outdoor PMV normal?
Is indoor PMV normal?
(A) Cooling
Is there clogging of indoor
air filter or heat exchanger?
Is there clogging of
outdoor heat exchanger?
Is connector connection
or coil normal?
Check indoor P.C. board.
Failure
→
Replace
Repair faulty parts.
Repair faulty parts.
Replace PMV body.
Repair faulty parts.
Are following items concerned
to indoor fan motor normal?
1. Connector connection
2. Condenser
3. Motor
4. Fan
Cleaning
Check outdoor
I/F P.C. board.
Failure
→
Replace
Refrigerant shortage,
clogging, pipe deformed
Refrigerant shortage or
clogging or pipe deformed
(B) Heating
Cleaning
Is indoor fan system normal?
• Fan crack
• Fan coming-off
FILE NO. SVM-1