Error detected by TCC-LINK central control device
TCC-LINK: TOSHIBA Carrier Communication Link.
L09
—
—
SIM Indoor capacity unset
Indoor
L10
L10
—
SIM Outdoor capacity unset
I/F
L20
—
—
SIM Duplicated central control addresses
AI-NET,
Indoor
L28
L28
—
SIM Over No. of connected outdoor units
I/F
L29
L29
01: IPDU1 error
02: IPDU2 error
03: IPDU3 error
04: Fan IPDU error
05: IPDU1 + Fan IPDU error
06: IPDU2 + Fan IPDU error
07: All IPDU error
SIM No. of IPDU error
I/F
L30
L30 Detected indoor address
SIM Indoor outside interlock
Indoor
—
L31
—
—
Extended I/C error
I/F
P01
—
—
ALT Indoor fan motor error
Indoor
P03
P03
—
ALT Discharge temp. TD1 error
I/F
P04
P04 01: Comp. 1 side
02: Comp. 2 side
ALT High-pressure SW system operation
IPDU
P05
P05 01: Phase-missing detection
02: Phase error
ALT Phase-missing detection /Phase error
I/F
P07
P07 01: Comp. 1 side
02: Comp. 2 side
ALT Heat sink overheat error
IPDU, I/F
P10
P10 Detected indoor address
ALT Indoor overflow error
Indoor
P12
—
—
ALT Indoor fan motor error
Indoor
P13
P13
—
ALT Outdoor liquid back detection error
I/F
P15
P15 01: TS condition
02: TD condition
ALT Gas leak detection
I/F
P17
P17
—
ALT Discharge temp. TD2 error
I/F
P19
P19 Detected outdoor unit number
ALT 4-way valve inverse error
I/F
P20
P20
—
ALT High-pressure protective operation
I/F
P22
P22
0
:IGBT short
1
:Fan motor position
detective circuit error
3
:Fan motor trouble
C :TH sensor temp. error
(Heat sink overheat)
D :TH sensor error
E
:Vdc output error
ALT Outdoor fan IPDU error
IPDU
P26
P26 01: Comp. 1 side
02: Comp. 2 side
ALT G-TR short protection error
IPDU
P29
P29 01: Comp. 1 side
02: Comp. 2 side
ALT Comp position detective circuit system
error
IPDU
P31
P31
—
ALT Other indoor unit error
(Group terminal unit error)
Indoor
—
—
—
By alarm device ALT
Error in indoor group
AI-NET
Check code
Wireless remote controller
Check code name
Judging
device
Central
control
device
indication
Outdoor 7-segment display
Sensor block display of
receiving unit
Auxiliary code
OPERATION TIMER PRE.DEF. Flash
C05
—
—
—
Sending error in TCC-LINK central
control device
TCC-LINK
C06
—
—
—
Receiving error in TCC-LINK central
control device
TCC-LINK
C12
—
—
—
Batch alarm of general-purpose
equipment control interface
General-
purpose
equipment I/F
P30
Differs according to error contents of unit with occurrence of alarm Group control branching unit error
TCC-LINK
—
—
(L20 is displayed.)
Duplicated central control addresses
+1111050501_01EN_SMMS_HighWall_IM_B5.book Page 29 Wednesday, November 12, 2008 2:45 PM
Toshiba
WARNINGS ON REFRIGERANT LEAKAGE
Check of Concentration Limit
The room in which the air conditioner is to be
installed requires a design that in the event of
refrigerant gas leaking out, its concentration will
not exceed a set limit.
The refrigerant R410A which is used in the air
conditioner is safe, without the toxicity or
combustibility of ammonia, and is not restricted by
laws to be imposed which protect the ozone layer.
However, since it contains more than air, it poses the
risk of suffocation if its concentration should rise
excessively. Suffocation from leakage of R410A is
almost non-existent. With the recent increase in the
number of high concentration buildings, however, the
installation of multi air conditioner systems is on the
increase because of the need for effective use of floor
space, individual control, energy conservation by
curtailing heat and carrying power etc.
Most importantly, the multi air conditioner system is
able to replenish a large amount of refrigerant
compared with conventional individual air
conditioners. If a single unit of the multi conditioner
system is to be installed in a small room, select a
suitable model and installation procedure so that if the
refrigerant accidentally leaks out, its concentration
does not reach the limit (and in the event of an
emergency, measures can be made before injury can
occur).
In a room where the concentration may exceed the
limit, create an opening with adjacent rooms, or install
mechanical ventilation combined with a gas leak
detection device.
The concentration is as given below.
The concentration limit of R410A which is used in multi
air conditioners is 0.3kg/m³.
▼
NOTE 1
If there are 2 or more refrigerating systems in a single
refrigerating device, the amounts of refrigerant should
be as charged in each independent device.
For the amount of charge in this example:
The possible amount of leaked refrigerant gas in
rooms A, B and C is 10kg.
The possible amount of leaked refrigerant gas in
rooms D, E and F is 15kg.
▼
NOTE 2
The standards for minimum room volume are as
follows.
(1) No partition (shaded portion)
(2) When there is an effective opening with the
adjacent room for ventilation of leaking refrigerant
gas (opening without a door, or an opening 0.15%
or larger than the respective floor spaces at the top
or bottom of the door).
(3) If an indoor unit is installed in each partitioned
room and the refrigerant piping is interconnected,
the smallest room of course becomes the object.
But when a mechanical ventilation is installed
interlocked with a gas leakage detector in the
smallest room where the density limit is exceeded,
the volume of the next smallest room becomes the
object.
▼
NOTE 3
The minimum indoor floor area compared with the
amount of refrigerant is roughly as follows: (When the
ceiling is 2.7m high)
Total amount of refrigerant (kg)
Min. volume of the indoor unit installed room (m³)
Concentration limit (kg/m)
Outdoor unit
e.g., charged amount
(15kg)
e.g., charged
amount
(10kg)
Indoor unit
Room A Room B Room C Room D Room E Room F
Outdoor unit
Refrigerant piping
Indoor unit
Refrigerant piping
Outdoor
unit
Indoor unit
Mechanical ventilation device - Gas leak detector
Very
small
room
Small
room
Medium
room
Large
room
0
5
10
10
20
30
15
20
25
30
35
40
Range below the
density limit of
0.3 kg/m³
(countermeasures
not needed)
Range above the
density limit of
0.3 kg/m³
(countermeasures
needed)
M
in
. i
ndo
or f
loor ar
ea
Total amount of refrigerant