11-5. Judgment of Trouble by Symptom
11-5-1. Indoor Unit (Including Remote Controller)
(1) Power of indoor unit does not turned on
• Be sure to disconnect the motor connector CN301 after shut off the power supply, or it will be a cause of
damage of the motor.
(2) Power of indoor unit does not turned on though Indoor P.C. board is replaced
<Primary check>
1. Is the supply voltage normal?
2. Is the normal voltage provided to the outdoor unit?
3. Is the crossover cable connected properly?
4. Is the fuse (F01) blown?
Turn off power supply once, and
60 second later, turn it on again.
Is OPERATION indicator flashing?
Is it possible to turn on
power supply by pushing
[START/STOP] button
on remote controller?
Does transmission mark
on remote controller flash
normally, and is its signal
transmitted properly?
Unit operates normally.
Remote controller is defective.
Refer to (5) “Troubleshooting
for remote controller”.
Does fan
motor connector
between CN301
–
short-circuit?
Parts (R01, R02, DB01,
C01, C03, IC01 and T101)
are defective.
Is fuse (F01)
of indoor control
board blown?
Is voltage
(DC12V or 5V)
indicated on rear of
indoor control
board normal?
Is DC310–340V
supplied between
CN10
–
?
Parts of a power supply circuit
defective.
Microcomputer
is defective.
Replace main
P.C. board.
Replace fan
motor.
Operation
Check Item
Considerable principle cause
Measures
Item by symptoms
YES
YES
YES
YES
YES
YES
YES
NO
NO
NO
NO
NO
NO
NO
<Confirmation procedure>
Turn on power supply.
Does OPERATION indicator flash?
Is wired correctly to white and
black lead wires of terminal block?
Correct wiring.
To item of
“Power supply is not turned on”.
YES
NO
YES
NO