– 104 –
Check
code
Outdoor
LED display
Check and troubleshooting
(Item without special mention indicates part of outdoor unit.)
[07]
[Case thermo operation, Power supply error]
[14]
[Short-circuit of compressor drive element]
[16]
[Position detection circuit error]
[17]
[Current detection circuit error]
Is AC mains voltage correct?
(198 to 264V)
Are CN609 of P.C. board MCC-1571
connection and case thermostat correct?
Short each pins of CN609.
Can compressor operate?
Is there gas leak?
Is there refrigerant shortage?
Is service valve fully opened?
Is PMV under correct conditions?
Confirm power supply
construction. etc.
Correct connector.
Case thermostat error
→
Replace.
Check ourdoor P.C.B MCC-1571.
Defect
→
Replace.
Repair defective position.
Recharge refrigerant.
Open service valve fully.
Correct defective position.
Replace defective part.
Check crushed or broken pipe.
Defect
→
Correct and Replace.
NO
NO
NO
NO
NO
NO
YES
YES
YES
YES
YES
YES
Are connections of
compressor lead and reactor correct?
(Check referring to the Wiring diagram.)
NO
YES
YES
NO
Does the same error occur in operation
without compressor lead?
Correct wiring.
Replace outdoor P.C.B MCC-1571.
Check compressor. (Rare short, etc.)
Defect
→
Replace.
Check outdoor P.C.B MCC-1571.
Defect
→
Replace.
Check outdoor P.C.B MCC-1571.
Defect
→
Replace.