– 98 –
(3) Only the indoor motor fan does not operate
<Primary check>
1. Is it possible to detect the power supply voltage (AC220–240V) between • and , on the terminal block?
2. Does the indoor fan motor operate in cooling operation?
(In heating operation, the indoor fan motor does not operate for approximately 10 minutes after it is
turned on, to prevent a cold air from blowing in.)
Turn off power
supply once, and
turn it on again.
Replace indoor
fan motor.
Start to operate
indoor unit in cooling
operation at airflow
level “LOW”.
Does fan motor
continue to operate?
Is it possible to detect
DC 1V or more between
and
of
motor connector (CN301)?
Does indoor
fan operate?
Is it possible to detect
DC 15V between
and
of
motor
connector (CN301)?
Turn off indoor unit and remove
connector from motor.
Then push START/STOP button
on remote controller to stop
flashing lamp on indoor unit.
Change airflow level
to “HIGH”.
Replace main
P.C. board.
Turn off indoor unit and
remove connector from motor.
Then start to operate indoor
unit with remote controller.
Replace
bearing.
Fan motor
operates normally.
Start to operate the
indoor unit in except
heating operation.
At this time, is it possible to
detect DC 1V or more between
and
of
motor
connector (CN301)?
Start to operate the
indoor unit in except
heating operation.
At this time, is it possible
to detect DC 1V or more
between
and
of motor connector (CN301)?
(Check this condition
within 15 seconds after
starting unit.)
Is it possible to
change airflow level
to “HIGH”?
Is it possible to
rotate cross-flow fan by
hand properly?
Turn off indoor unit
and rotate cross-flow
fan by hand when the
unit is on standby.
At this time, is it possible to
detect DC 1V or more
between
and
of motor connector
(CN301)?
Is it possible to detect
DC 310?340V between
and
of motor
connector (CN301)?
(Motor connection condition)
Is it possible to detect DC 15V
between
and
of
motor connector (CN301)?
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO