– 53 –
2. Indoor fan
motor control
(Continued)
Item
Operation flow and applicable data, etc.
Description
[In starting and in stability]
In starting
In stability
FAN AUTO
• Until 12 minutes passed after operation start
• When 12 to 25 minutes passed after operation start
and room temp. is 3°C or lower than set temp.
• When 12 to 25 minutes passed after operation start and
room temp. is higher than (set temp. –3°C)
• When 25 minutes or more passed after operation start
FAN Manual
• Room temp. < Set temp. –4°C
• Room temp.
≥
Set temp. –3.5°C
(Table 2) Indoor fan air flow rate (Heating)
Fan speed level
RAS-M10PKVP-E
RAS-M13PKVP-E
RAS-M16PKVP-E
RAS-M18PKVP-E
Fan speed
(rpm)
Air flow rate
(m
3
/h)
Fan speed
(rpm)
Air flow rate
(m
3
/h)
Fan speed
(rpm)
Air flow rate
(m
3
/h)
Fan speed
(rpm)
Air flow rate
(m
3
/h)
WF
1140
640
1200
690
1280
750
1390
805
WE
UH
1140
640
1200
690
1280
750
1390
805
WD
H
1070
590
1100
610
1180
670
1290
730
WC
M+
980
530
1010
550
1090
610
1180
655
WB
900
470
930
490
980
530
1070
575
WA
M
850
430
850
430
900
470
980
510
W9
810
400
810
400
880
450
950
490
W8
L+
710
330
710
330
780
380
850
420
W7
L
710
330
710
330
710
330
850
420
W6
L–
650
290
650
290
700
320
700
310
W5
UL
650
290
650
290
650
290
650
275
W4
650
290
650
290
650
290
650
275
W3
SUL
650
290
650
290
650
290
650
275
W2
560
220
560
220
560
220
560
210
W1
420
120
420
120
420
120
420
110