– 66 –
Item
Operation flow and applicable data, etc.
Description
19. Set temperature
correction
Indoor Control P.C. Board (Factory Default)
1. Purpose
When the difference between the set temp. of
the remote controller and the room temp. is
wide due to the installation condition, etc, the
set temp. is corrected.
(HEAT operation only)
2. Description
The set temp. received from the remote
controller is corrected.
The correct value from –2°C to +4°C is changed
by the jumper wire on P.C. board of the indoor
microcomputer.
20. Various setting
on outdoor unit
(Power save,
Cooling-only,
etc.)
The following settings are available by DIP switch setup.
Jumper wire
In HEAT Operation
Jumper wire setup
HEAT
shift value
: With Jumper wire
: Cut Jumper wire
Caution:Set the switch before turning on the power supply.
Function
Setting position
Control contents
Power save
setup
Turn the switch to ON, when using the power save function.
Cooling-only
setup
When using the air conditioner as a cooling-only conditioner,
turn the switch to ON.
(If the heating mode is selected by remote control, outdoor
unit will remain stop. If mixed with indoor unit cooling and
heating, outdoor unit performs cooling operation.)
Heating-only
setup
When using the air conditioner as a heating-only conditioner,
turn the switch to ON.
(If the cooling mode is selected by remote control, outdoor
unit will remain stop. If mixed with indoor unit cooling and
heating, outdoor unit performs heating operation.)
Power save function
Select current limit
Cooling only setting
Heating only setting
SW802
No.1
OFF
ON
ON
OFF
No.2
ON
ON
OFF
OFF
Current limit
11A
8.5A
Full
Full (Default)
←
At shipment