– 103 –
11-6. Trouble Diagnosis by Outdoor LED
For the outdoor unit, the self-diagnosis is possible by LED (Green) and five LEDs (Red).
∗
LED (Green)(D800) and LEDs (Red)(D801 to D805) are provided on the control P.C. board MCC-5071.
1. If there is an error, LED (Red or Green) goes on or flashes according to the error as described in the below
table.
2. When there are two or more errors, LEDs go on cyclically.
3. Usually, LED (Green)(D800) goes on.
PMV. : Pulse Motor Valve
∗
1: Back-up operation is performed without error display of the indoor unit.
∗
2: Operated normally when the air conditioners in other rooms are driven.
LED display
Indoor
check code
Description
D800
D801
D802
D803
D804
D805
—
During normal operation
07
Case thermo. operation, Power supply error
14
Driving element short-circuit
16
Position detection circuit error
17
Current detection circuit error
1C
Compressor system error, Compressor lock
19
Discharge temp. sensor (TD) error
1A
Fan system error
∗
1
1B
Outside temp. sensor (TO) error
1D
Compressor lock
1E
Discharge temp. error, gas leakage
1F
Compressor break down
18
Suction temp. sensor (TS) error
18
Heat exchanger temp. sensor (TE) error
∗
2
1C
A room gas side temp. sensor (TGa) error
∗
2
1C
B room gas side temp. sensor (TGb) error
∗
2
1C
C room gas side temp. sensor (TGc) error
1C
Gas leak detection, PMV error
1C
Communication error between MCU
1C
Communication error between MCU
1C
Communication error between MCU
20
PMV error for A room
20
PMV error for B room
20
PMV error for C room
(Legend)
D800 (Green)
D801 (Red)
D802 (Red)
D803 (Red)
D804 (Red)
D805 (Red)
: Go off,
: Go on,
: Flash