– 109 –
Check
code
Outdoor
LED display
Check and troubleshooting
(Item without special mention indicates part of outdoor unit.)
[1F]
[Compressor break down]
[20]
∗
There is a possibility that it is one of the following errors.
Confirm LED on outdoor P.C. board to judge which error it is.
PMV error for A room, B room, C room
[PMV error for A room]
[PMV error for B room]
[PMV error for C room]
YES
Is AC mains voltage correct?
(198 to 264V)
Check wiring construction.
Ask repair of power supply.
NO
YES
YES
NO
NO
Is wire connection correct?
Compressor lead
(Board side, Compressor Side),
Reactor lead, Power supply lead.
Does an abnormal overload happen?
Check wire connection
and correct it.
Remove and improve
the cause of overload.
Check outdoor P.C.B MCC-1571.
Defect
→
Replace.
Is PMV under correct conditions?
Repair defective position.
Replace defective part.
NO
YES
Check temp. sensor of A room indoor unit?
TA sensor, TC sensor
Correct connector.
Sensor error
→
Replace.
Check outdoor P.C.B. MCC-5071
and indoor A room P.C. board.
Defect
→
Replace.
OK
Error
Is PMV under correct conditions?
Repair defective position.
Replace defective part.
NO
YES
OK
Error
Correct connector.
Sensor error
→
Replace.
Check outdoor P.C.B. MCC-5071
and indoor B room P.C. board.
Defect
→
Replace.
Check temp. sensor of B room indoor unit?
TA sensor, TC sensor
Is PMV under correct conditions?
Repair defective position.
Replace defective part.
NO
YES
Check temp. sensor of C room indoor unit?
TA sensor, TC sensor
Correct connector.
Sensor error
→
Replace.
Check outdoor P.C.B. MCC-5071
and indoor C room P.C. board.
Defect
→
Replace.
Error
OK