46
Check code
Operation cause
[21]
1. Inverter high pressure SW error.
Inverter high pressure SW system alarm
2. Inverter IOL operation.
3. Service valve closed.
4. Outdoor fan, capacitor error.
5. Indoor/Outdoor PMV blockage.
6. Outdoor heat exchanger blockage.
7. SV2 circuit blockage.
8. Indoor – Outdoor communication error.
9. Pd sensor error.
10. Refrigerant overcharge.
Does the inverter high pressure
switch operate?
Are the inverter high pressure
switch parts normal?
Is service valve fully open?
Does the cooling outdoor fan
normally operate?
Is there a problem with the
outdoor unit heat exchanger?
(1) Blockage of heat exchanger
(2) Short circuit
Il circuito di bypass della SV2 è normale?
Is SV2 bypass circuit normal?
A
Check parts.
If defective, replace.
Open service valve fully.
Remove cause.
Repair SV2 bypass circuit.
Are the connection, capacitor
and fan motor normal?
Are the high pressure sensor
characteristics normal?
See judgment flow of IPDU IOL
operation circuit “E5”.
Repair defective position.
Replace high pressure sensor.
Check outdoor IPDU PC board.
If defective, replace board.
Is the inverter IOL
circuit normal?
Is circuit wiring normal?
Check and modify wiring
j
j
j
j
j
j
j
j
j
j
j
j
j
j
j
j
j
j
j
j
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No
No
No
No
No
No
No
No
No
No
Troubleshooting
Diagnostic procedure for check code
(Coil error, disconnection of wiring, etc.)
Summary of Contents for HFC R407C
Page 1: ...A90 0233 HFC R407C Super Multi System Service Manual Air Conditioner Multi Split Type System ...
Page 2: ...2 ...
Page 18: ...18 Wiring diagrams Outdoor unit MAR F105HTM8 PE ...
Page 19: ...19 Wiring diagrams Outdoor unit ...
Page 21: ...21 Refrigeration piping schematic diagram Outdoor unit ...
Page 74: ...74 Exploded view and service parts Outdoor unit ...
Page 75: ...75 Exploded view and service parts Outdoor unit 12 14 j ...
Page 80: ...www toshiba aircon co uk MADE IN UK A90 0233 Revised October 2002 ...