Valve and sensor function and operation
Outdoor unit
Outdoor unit - valve functions
Symbol
Name of valve
Description of function
20SF
4-way reversing valve
OFF: Normal operation.
(4-way valve)
Cooling operation
ON: Low load condition when sub heat exchanger is
required. Used in combination with SV15.
4-way reversing valve
ON: Normal operation.
Heating operation
OFF: Defrost operation.
SV1
High-pressure release
Heating operation.
solenoid valve
Energised when TE >11°C
SV2
Hot gas bypass solenoid
Opens when Pd < 13 kgf/cm
2
G (ccoling)
valve
(For cooling-dominant mode and sub heat exchanger
operation Pd < 17 kgf/cm
2
G - 3-pipe only).
Opens when outdoor ThO < 0°C
SV4
Solenoid valve for D.O.L.
Opens when the D.O.L. compressor starts for
compressor start-up
unloading.
SV5
Gas balance
Opens when compressor stops.
SV13
Cooling solenoid valve
Opens for cooling-only operations.
SV14
Solenoid valve for
SV14 opens for heating operation.
expansion valve.
SV15
Sub heat exchanger
Opens for sub heat exchanger requirement.
solenoid valve
SV16
Solenoid valve for capillary
SV16 opens for low load conditions during heating-
dominant operation.
SV17
Solenoid valve for compressor Open when compressor ON.
Closed when compressor OFF.
PMV1
Cooling bypass flow
Opens when ThD1 or ThD2 > 110°C.
control valve
Opens when ThS > 20°C.
PMV2
Outdoor flow control valve
Opens during cooling-dominant operation.
Degree of opening depending on cooling/heating
demands.
Summary of Contents for HFC R407C
Page 1: ...A90 0233 HFC R407C Super Multi System Service Manual Air Conditioner Multi Split Type System ...
Page 2: ...2 ...
Page 18: ...18 Wiring diagrams Outdoor unit MAR F105HTM8 PE ...
Page 19: ...19 Wiring diagrams Outdoor unit ...
Page 21: ...21 Refrigeration piping schematic diagram Outdoor unit ...
Page 74: ...74 Exploded view and service parts Outdoor unit ...
Page 75: ...75 Exploded view and service parts Outdoor unit 12 14 j ...
Page 80: ...www toshiba aircon co uk MADE IN UK A90 0233 Revised October 2002 ...