Introduction
Components
Setting of indoor unit capacity codes
•
The setting of the indoor unit capacities is important. Set the correct indoor unit code numbers
according to the indoor unit capacity. The capacities are set by the rotary switches on the printed
circuit board switch A (unit A), switch B (unit B), switch C (unit C) and switch D (unit D).
•
During manufacture, the indoor capacity selection switches are set at ‘0’.
•
Record the indoor capacity codes, indoor unit model names and locations in the installation manual,
and on the wiring diagram on the electrical panel cover.
Example:
Room A
Room B
Room C
Capacity 16
Capacity 16
Capacity 26
Indoor unit
Capacity
No connection
10
13
16
20
26
36
46
Code number
0
2
3
4
5
6
8
10
(Example: Model RAV-364UH-PE, capacity = 36)
Multi Controller PCB
MCC-1210
Capacity select switches
•
Multiple indoor units may be connected to each outdoor unit, providing the total indoor code does not
exceed the limits shown below.
Combination of Multi Controllers and indoor units
Number of
Maximum No. of
Indoor unit diversity
Maximum system code
Maximum code per
Multi Controllers
indoor units
Multi Controller
1
4
135%
27
27
2
8
160%
32
27
3
12
27 (13*)
4
16
13
Example of systems with maximum possible code:
OD
OD
DIF
DIF
DIF
27
13
OD
27
27
13
13
13
13
13
OD
27
Outdoor unit
Interface kit
Multi Controller [code]
(Max. system code)
OD
OD
OD
OD
DIF
DIF
DIF
27
26
6
6
6
8
8
8
8
20
(27)
(32)
(32)
(32)
Summary of Contents for HFC R407C
Page 1: ...A90 0233 HFC R407C Super Multi System Service Manual Air Conditioner Multi Split Type System ...
Page 2: ...2 ...
Page 18: ...18 Wiring diagrams Outdoor unit MAR F105HTM8 PE ...
Page 19: ...19 Wiring diagrams Outdoor unit ...
Page 21: ...21 Refrigeration piping schematic diagram Outdoor unit ...
Page 74: ...74 Exploded view and service parts Outdoor unit ...
Page 75: ...75 Exploded view and service parts Outdoor unit 12 14 j ...
Page 80: ...www toshiba aircon co uk MADE IN UK A90 0233 Revised October 2002 ...