Troubleshooting
Diagnostic procedure for check code
Check code
Status of air conditioner
Operation cause
[04]
Outdoor unit stops
1. Wiring fault between indoor and Multi
Inverter serial signal
Indoor unit fan continues
Controller or Multi Controller and outdoor
short circuit
interface PC board.
Inter-unit communication
2. Defective communication PC board.
3. Defective IPDU PC board.
4. Noise from outside.
5. High level refrigeration leak (RBC-RD2-PE).
Is there continuity of the
communication cable between
the indoor unit and Multi
Controller?
Replace communication cable
h
j
Yes
No
Is there continuity of the
communication cable between
the Multi Controller the outdoor
unit
Replace communication cable
h
No
Is there continuity of the
communication cable between
the outdoor interface PC board
and outdoor IPDU PC board?
Replace communication cable
h
No
Is there voltage present
between pins 4 and 5 of CN1
on communication PC board?
(DC 0 to 5 V, pin 5-GND)
Communication PC board is defective - replace
h
No
Is there voltage present
between pins 3 and 5 of CN1
on interface PC board?
(DC 0 to 5 V, pin 5-GND)
IPDU PC board is defective - replace
h
No
j
Yes
j
Yes
j
Yes
j
Yes
Check noise interference from
outside, etc.
j
Yes
Is refrigerant detector
RBC-RD2-PE fitted?
Complete checks detailed above
h
No
j
Yes
Are the high level alarm and
the shutdown LEDs on the
RBC-RD2-PE (RED) on?
Complete checks detailed above
h
No
j
Yes
Refrigerant leak.
Leak-check unit.
Summary of Contents for HFC R407C
Page 1: ...A90 0233 HFC R407C Super Multi System Service Manual Air Conditioner Multi Split Type System ...
Page 2: ...2 ...
Page 18: ...18 Wiring diagrams Outdoor unit MAR F105HTM8 PE ...
Page 19: ...19 Wiring diagrams Outdoor unit ...
Page 21: ...21 Refrigeration piping schematic diagram Outdoor unit ...
Page 74: ...74 Exploded view and service parts Outdoor unit ...
Page 75: ...75 Exploded view and service parts Outdoor unit 12 14 j ...
Page 80: ...www toshiba aircon co uk MADE IN UK A90 0233 Revised October 2002 ...