44
Check code
Status of air conditioner
Operation cause
[1d]
Operation stops
1. Outdoor unit power source error.
Compressor error alarm
2. Inverter compressor circuit system error.
Refer to outdoor unit
3. Inverter compressor error.
4. Inverter compressor refrigerant stagnation.
5. Defective IPDU PC board.
Troubleshooting
Diagnostic procedure for check code
Is the power source voltage of the
outdoor unit normal?
Does voltage reduction occur
when the fixed-speed compressor
has been activated?
Is the connection of wiring on
the IPDU PC board normal?
Is there an abnormal overload?
Is the inverter compressor normal?
Is there refrigerant stagnation
in the compressor case?
Check IPDU PC board.
Confirm the power source supply.
Modify connector wiring.
Modify cause of overload.
Compressor error
Modify refrigerant stagnation in
the compressor case, and start
the operation.
Is the inverter winding
output normal?
Check IPDU PC board.
j
j
j
j
j
j
j
h
h
h
h
h
h
i
No
No
No
No
No
No
No
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Summary of Contents for HFC R407C
Page 1: ...A90 0233 HFC R407C Super Multi System Service Manual Air Conditioner Multi Split Type System ...
Page 2: ...2 ...
Page 18: ...18 Wiring diagrams Outdoor unit MAR F105HTM8 PE ...
Page 19: ...19 Wiring diagrams Outdoor unit ...
Page 21: ...21 Refrigeration piping schematic diagram Outdoor unit ...
Page 74: ...74 Exploded view and service parts Outdoor unit ...
Page 75: ...75 Exploded view and service parts Outdoor unit 12 14 j ...
Page 80: ...www toshiba aircon co uk MADE IN UK A90 0233 Revised October 2002 ...