57
Troubleshooting
Diagnostic procedure for check code
Check code
Operation cause
[Ad]
1. Fixed-speed compressor high pressure SW error.
Fixed-speed compressor fault
2. Fixed-speed compressor IOL operation.
3. Service valve closed.
4. Outdoor fan, capacitor error.
5. Multi Controller/outdoor PMV blockage.
6. Outdoor heat exchanger blockage.
7. SV2 circuit blockage.
8. Miswiring of communicaiton between indoor and outdoor unit.
9. Pd sensor error.
10. Refrigerant overcharge.
OCR: Overload Current Relay
Does the fixed-speed high
pressure switch operate?
Are the fixed-speed high
pressure switch parts normal?
Is service valve fully open?
Does the outdoor fan
normally operate?
Is there a problem with the
outdoor unit heat exchanger?
(1) Blockage of heat exchanger
(2) Short circuit (air flow)
(3) Blockage of air flow
C
Check parts.
If defective, replace.
Open service valve fully.
Remove cause.
Are the connection, capacitor
and fan motor normal?
Are the high pressure sensor
characteristics normal?
See judgment flow of fixed-speed
IOL, OL circuits “E6”.
Check outdoor interface PC board.
If defective replace board.
Is the fixed-speed
IOL circuit normal?
Is circuit wiring normal?
Check and modify wiring
j
j
j
j
j
j
j
j
j
j
j
j
j
j
j
j
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No
No
No
No
No
No
No
Repair failed position.
j
No
Replace high pressure sensor.
j
No
Reset relay.
Check compressor withstand
resistance.
Is the fixed-speed
OCR circuit normal?
j
j
Yes
No
j
Summary of Contents for HFC R407C
Page 1: ...A90 0233 HFC R407C Super Multi System Service Manual Air Conditioner Multi Split Type System ...
Page 2: ...2 ...
Page 18: ...18 Wiring diagrams Outdoor unit MAR F105HTM8 PE ...
Page 19: ...19 Wiring diagrams Outdoor unit ...
Page 21: ...21 Refrigeration piping schematic diagram Outdoor unit ...
Page 74: ...74 Exploded view and service parts Outdoor unit ...
Page 75: ...75 Exploded view and service parts Outdoor unit 12 14 j ...
Page 80: ...www toshiba aircon co uk MADE IN UK A90 0233 Revised October 2002 ...