13
Parts specification
Outdoor unit
Specification of outdoor unit refrigeration cycle parts
Parts description
MAR-F105HTM8-PE
Compressor model
Model name
MG1300CW-20
Motor type
3-phase induction motor
Power supply
380-415 V, 3 phase, 50 Hz
Output
kW
7.5
Pole
2/2 (inverter side/non-inverter side)
Coil resistance
Ω
1.49/2.51 (inverter side/non-inverter side)
Compressor oil name
Polyolester NISSEKI RB68AF VG 74
Amount of oil
ml
7,000
Fan motor
Model name
STF-200-350A
Motor type
1-phase, induction type
Power supply
220-240 V, 1 phase, 50 Hz
Output
kW
0.4
Supply current
A
3.2 ~ 3.5
Pole
6
Protective device
Operation
°C
145 ± 5
(Relay)
Reset
°C
86 ± 15
High pressure switch
Model name
ACB-JB128
Inverter side
Operating pressure
Operation
MPa
3.2
Reset
MPa
2.55
High pressure switch
Model name
ACB-JA64
Fixed side
Operating pressure
Operation
MPa
3.2
Reset
MPa
2.55
Low pressure switch
Model name
20PS-1
Operating pressure
Operation
MPa
0.025
Reset
MPa
0.15
4-way valve
CHV-0712, coil AC240 V
Liquid tank
l
(RSH 12) 12
Accumulator
l
(BT9-1 1/8)
Check valve
Model name
YCV5-3SPTF-1
Maximum pressure
MPa
3.3
Check joint
Model name
R-407C type
Maximum pressure
MPa
3.53
Expansion valve
EXV-V-E80HTF-9WS
Compressor heater
(Internal within the compressor)
Accumulator heater
W
29 (240 V AC)
Pressure sensor
Model name: NTP-Q250TF-2
Input voltage: DC12 V
Output voltage: DC 0.5 - 4.5 V
Discharge temperature sensor
25°C = 50 k
Ω
50°C = 18.1 k
Ω
100°C = 3.35 k
Ω
Suction temperature sensor/
0°C = 34.6 k
Ω
outdoor air temperature sensor
25°C = 10 k
Ω
50°C = 3.4 k
Ω
Pulse modulating valve (Cooling bypass PMV1)
EV18RC1, coil DC 12 V
Pulse modulating valve (PMV2)
EV23RC2, coil DC 12 V
2-way valve (SV1, SV2, SV4, SV5, SV16, SV17)
NEV202DXF, coil AC 240 V
2-way valve (SV13, SV14, SV15)
RP100-03, coil AC 240 V
Note:
Specifications are subject to change without notice.
Summary of Contents for HFC R407C
Page 1: ...A90 0233 HFC R407C Super Multi System Service Manual Air Conditioner Multi Split Type System ...
Page 2: ...2 ...
Page 18: ...18 Wiring diagrams Outdoor unit MAR F105HTM8 PE ...
Page 19: ...19 Wiring diagrams Outdoor unit ...
Page 21: ...21 Refrigeration piping schematic diagram Outdoor unit ...
Page 74: ...74 Exploded view and service parts Outdoor unit ...
Page 75: ...75 Exploded view and service parts Outdoor unit 12 14 j ...
Page 80: ...www toshiba aircon co uk MADE IN UK A90 0233 Revised October 2002 ...