12
Parts specification
Outdoor unit
Specification of 3-pipe, heat recovery outdoor unit
Model name
MAR-F105HTM8-PE
Cooling capacity
kW
25.0 (28.0)
Heating capacity
kW
28.0 (31.5)
Power supply
380-415 V, 3 phase, 50 Hz
Cooling
Operating current
A
17.4 (19.1)
Power consumption
kW
11.8 (12.8)
EER
2.11 (2.19)
Power factor
%
98 (97)
Heating
Operating current
A
17.7 (15.5)
Power consumption
kW
11.8 (10.5)
COP
2.37 (3.0)
Power factor
%
96 (98)
Starting current
A
60
Starting method
Direct
Sound level
Sound pressure
dB
58
Sound power
dB(A)
70
Dimensions (H x W x D)
mm
1700 x 990 x 790
Net weight
kg
285
Colour
Silky Shade (Munsell 1-Y8.5/0.5)/RAL 1013 (DE ~9)
Compressor
Type
Hermetically sealed (twin scroll)
Oil (volume)
ml
Polyolester NISSEKI RB74AF 74VG (7000)
Crankcase heater
Internal type
Motor output
kW
7.5
Fan assembly
Fan
Propeller fan
Motor output
kW
0.4
Air flow volume
m
3
/h
10,000
Refrigeration (charged weight)
kg
R-407C (19)
Piping connection
Liquid
mm
15.9 (flare connection)
Discharge gas
mm
19.0 (flare connection)
Suction gas
mm
28.6 (brazing connection)
Max. equivalent piping length
m
120
Max. actual piping length
m
100
Max. piping head
m
50: when the outdoor unit is installed above
m
20: when the outdoor unit is installed below
Suction accumulator case heater
W
29 (240 V AC)
Notes:
1.
Specifications are subject to change without notice.
2.
The specification shown in ( ) denotes operation with an indoor unit load diversity of 135%.
3.
Operating conditions:
Outdoor temperature °C
Cooling
-5 to 43
Heating
-15 to 21
Room temperature °C
Cooling
18 to 32
Heating
15 to 29
4.
Sound level: 1 m horizontal from centre.
1.5 m vertical from base.
Summary of Contents for HFC R407C
Page 1: ...A90 0233 HFC R407C Super Multi System Service Manual Air Conditioner Multi Split Type System ...
Page 2: ...2 ...
Page 18: ...18 Wiring diagrams Outdoor unit MAR F105HTM8 PE ...