Introduction
Operating conditions
•
Operating conditions of the unit are as follows:
Outdoor temperature
-5 ~ 43°C
Cooling
-15 ~ 21°C
Heating
Room temperature
18 ~ 32°C
Cooling
15 ~ 29°C
Heating
Room humidity
<80%
Cooling
Note 1: Cooling capacity is rated at the following temperature conditions:
Indoor air inlet temperature
27°C DB, 19°C WB.
Outdoor air inlet temperature
35°C DB.
Note 2: Heating capacity is rated at the following temperature conditions:
Indoor air inlet temperature
20°C DB.
Outdoor air inlet temperature
7°C DB, 6°C WB.
Note 3: For details about the outdoor unit, indoor units or remote controller installation refer to the relevant
literature, i.e. Installation Instructions supplied with the units.
Note 4: Operatives handling refrigerants must be suitably qualified in accordance with local and national
codes of practice and statutory requirements.
Note 5: Legislation may regulate the removal of waste refrigerant from the systems. We advise
awareness of any regulations and duty of care. Waste refrigerant must NEVER be discharged to
atmosphere.
Note 6: Electrical work should be in accordance with all relevant codes of practice and should be carried
out by suitably qualified personnel.
Note 7: Metric/Imperial pipe conversion.
Diameter (mm)
6.4
9.5
12.7
15.9
19.0
22.0
28.6
Nominal diameter (inch)
1/4
3/8
1/2
5/8
3/4
7/8
1-1/8
Note 8: Within this manual:
ODU
= Outdoor Unit
IDU
= Indoor Unit
R/C
= Remote Controller
D.O.L.
= Direct On-Line compressor
INV
= Inverter ODU
WB
= Wet Bulb
DB
= Dry Bulb
IOL
= Inner Overload Relay
Mg-Sw = Magnetic Contactor
IGBT
= Inverter Gate Bi-Polar Transistor
OCR
= Over Current Relay
IPDU
= Intelligent Power Drive Unit
M/C
= Multi Controller
Note 9: MPaG
⇒
kgf/cm
2
G conversion multiplier
1.0 MPaG = 10.2 kgf/cm
2
G
Summary of Contents for HFC R407C
Page 1: ...A90 0233 HFC R407C Super Multi System Service Manual Air Conditioner Multi Split Type System ...
Page 2: ...2 ...
Page 18: ...18 Wiring diagrams Outdoor unit MAR F105HTM8 PE ...
Page 19: ...19 Wiring diagrams Outdoor unit ...
Page 21: ...21 Refrigeration piping schematic diagram Outdoor unit ...
Page 74: ...74 Exploded view and service parts Outdoor unit ...
Page 75: ...75 Exploded view and service parts Outdoor unit 12 14 j ...
Page 80: ...www toshiba aircon co uk MADE IN UK A90 0233 Revised October 2002 ...