Troubleshooting
Diagnostic procedure for check code
Check code
Status of air conditioner
Operation cause
[99]
Indoor unit stops
1. Remote controller circuit connection error.
Remote controller serial
2. Duplicated indoor No.1 units.
signal circuit alarm
3. Remote controller error.
4. Indoor PC board error.
Are A, B, C internal wires normal?
Check connection of wiring.
j
h
No
Yes
Is there a connection error?
Yes
No
Set SW01 to 1.
Correct switch SW01.
h
h
Is SW01 set to No. 1 on
the master unit?
Is SW01 duplicated?
Check indoor PC board.
If defective, replace.
No
No
Yes
Yes
j
Does the indoor unit operate?
Is SW01 set to No. 1?
Make unit set-up No.1.
j
h
No
Yes
j
j
Is group operation performed?
Yes
No
h
j
Check indoor PC board.
If defective, replace.
Check remote controller.
If defective, replace.
h
h
Does serial LED (Green)
D15 on the indoor PC board
flash?
Does serial LED (Orange)
D14 on the indoor PC
board flash?
No
Yes
No
Yes
j
j
No
j
Yes
g
i
Summary of Contents for HFC R407C
Page 1: ...A90 0233 HFC R407C Super Multi System Service Manual Air Conditioner Multi Split Type System ...
Page 2: ...2 ...
Page 18: ...18 Wiring diagrams Outdoor unit MAR F105HTM8 PE ...
Page 19: ...19 Wiring diagrams Outdoor unit ...
Page 21: ...21 Refrigeration piping schematic diagram Outdoor unit ...
Page 74: ...74 Exploded view and service parts Outdoor unit ...
Page 75: ...75 Exploded view and service parts Outdoor unit 12 14 j ...
Page 80: ...www toshiba aircon co uk MADE IN UK A90 0233 Revised October 2002 ...