H9 ASD Installation and Operation Manual
193
Adding Input Selection
Program
⇒
Feedback
⇒
Override Control
This parameter Enables/Disables the feature that allows for the external
adjustment of the Output Frequency.
Selecting either of the input methods listed enables this feature. The selected
input is used as a modifier of the programmed Output Frequency.
Settings:
0 — Disabled
1 — V/I
2 — RR
3 — RX
4 — Panel Keypad
5 — RS485 (2-wire)
6 — RS485 (4-wire)
7 — Communication Option Board
8 — RX2 Option (AI1)
9 — Option V/I
10 — UP/DOWN Frequency (terminal board)
11 — Pulse Input (option)
12 — Pulse Input (Motor CPU)
13 — Binary/BCD Input (option)
Direct Access Number — F660
Parameter Type — Selection List
Factory Default — Disabled
Changeable During Run — Yes
Multiplying Input Selection
Program
⇒
Feedback
⇒
Override Control
This parameter Enables/Disables the feature that allows for the external
adjustment of the Output Frequency.
Selecting either of the input methods listed enables this feature. The selected
input is used as a multiplier of the programmed Output Frequency.
If operating using the LED Keypad Option and Setting is selected, the value
entered at
F729
is used as the multiplier.
Settings:
0 — Disabled
1 — V/I
2 — RR
3 — RX
4 —
F729
(setting)
5 — RX2 Option (AI1)
Direct Access Number — F661
Parameter Type — Selection List
Factory Default — Disabled
Changeable During Run — No
F660
F661