152
H9 ASD Installation and Operation Manual
Autotuning 2
Program
⇒
Motor
⇒
Vector Motor Model
This parameter introduces a thermal element into the autotuning equation and is
used to automatically adjust the Autotune parameter values as a function of
increases in the temperature of the motor.
Settings:
0 — Off
1 — Self-Cooled Motor Tuning
2 — Forced Air Cooled Motor Tuning
Direct Access Number — F402
Parameter Type — Selection List
Factory Default — Off
Changeable During Run — No
Motor Rated Capacity
Program
⇒
Motor
⇒
Vector Motor Model
This parameter is used to set the (nameplated) rated capacity of the motor being
used.
Direct Access Number — F405
Parameter Type — Numerical
Factory Default — 11.0
Changeable During Run — Yes
Minimum — 0.1
Maximum — 500.00
Units — kW
Motor Rated Current
Program
⇒
Motor
⇒
Vector Motor Model
This parameter is used to set the (nameplated) current rating of the motor being
used.
Direct Access Number — F406
Parameter Type — Numerical
Factory Default — 20.3
Changeable During Run — Yes
Minimum — 0.1
Maximum — 2000.0
Units — Amps
Motor Rated RPM
Program
⇒
Motor
⇒
Vector Motor Model
This parameter is used input the (nameplated) rated speed of the motor.
Direct Access Number — F407
Parameter Type — Numerical
Factory Default — 1730
Changeable During Run — Yes
Minimum — 100
Maximum — 60000
Units — RPM
Base Frequency Voltage 1
Program
⇒
Vector
⇒
Vector Motor Model
The Motor #1 Base Frequency Voltage 1 is the Motor #1 output voltage at the
Base Frequency (
F014
). Regardless of the programmed value, the output
voltage cannot be higher than the input voltage.
The actual output voltage will be influenced by the input voltage of the ASD
and the Supply Voltage Correction setting (
F307
).
Direct Access Number — F409
Parameter Type — Numerical
Factory Default — (ASD-dependent)
Changeable During Run — Yes
Minimum — 50.0
Maximum — 660.0
Units — Volts
F402
F409