88
H9 ASD Installation and Operation Manual
Option V/I Terminal Voltage/Current Selection
Program
⇒
Frequency
⇒
V/I Settings
This parameter is used to set the AI2 input terminal to receive either current or
voltage as a control signal.
Note:
The Expansion IO Card Option 2 option board (P/N ETB004Z)
is required to use this terminal.
See the Expansion IO Card Option 2 instruction manual (P/N 58686) for
more information on the function of this terminal.
Settings:
0 — Voltage Input
1 — Current Input
Direct Access Number — F109
Parameter Type — Selection List
Factory Default — Voltage Input
Changeable During Run — No
Always ON 1 Terminal 1
Program
⇒
Terminal
⇒
Input Terminals
⇒
ON
This parameter is used to set the functionality of the virtual discrete input
terminal ON. As a virtual terminal, the ON control terminal exists only in
memory and is considered to always be in its True (connected to CC) state.
It is often practical to assign a function to this terminal that the user desires to
be maintained regardless of external conditions or operations.
This parameter sets the programmable ON terminal to any one of the user-
selectable functions listed in
Table 5 on pg. 236
.
Direct Access Number — F110
Parameter Type — Selection List
Factory Default — Unassigned
Changeable During Run — No
Input Terminal 1 (F) Function
Program
⇒
Terminal
⇒
Input Terminals
This parameter is used to set the functionality of the F discrete input terminal.
In addition, this input terminal must be specified as Normally Open or
Normally Closed.
This parameter sets the programmable F terminal to any one of the user-
selectable functions listed in
Table 5 on pg. 236
.
Direct Access Number — F111
Parameter Type — Selection List
Factory Default—Forward
Forward
Changeable During Run — No
Input Terminal 2 (R) Function
Program
⇒
Terminal
⇒
Input Terminals
This parameter is used to set the functionality of the R discrete input terminal.
In addition, this input terminal must be specified as Normally Open or
Normally Closed.
This parameter sets the programmable R terminal to any one of the user-
selectable functions listed in
Table 5 on pg. 236
.
Direct Access Number — F112
Parameter Type — Selection List
Factory Default — Reverse
Reverse
Changeable During Run — No
Input Terminal 3 (ST) Function
Program
⇒
Terminal
⇒
Input Terminals
This parameter is used to set the functionality of the ST discrete input terminal.
In addition, this input terminal must be specified as Normally Open or
Normally Closed.
This parameter sets the programmable ST terminal to any one of the user-
selectable functions listed in
Table 5 on pg. 236
.
Direct Access Number — F113
Parameter Type — Selection List
Factory Default — Standby
Standby
Changeable During Run — No
F109
F113